Characteristic Data for PROFINET CBA
5.6.1
Typical Values and Limit Values
The CP supports PROFINET CBA interconnections between PROFINET CBA
components.
The ”typical” values specified below are values that cause the SIMATIC iMap
configuration tool to generate a warning if they are exceeded; it is nevertheless
possible that the configuration can be operated.
If one of the limit values specified for the interconnections is exceeded, they
cannot be downloaded to the module. When the interconnections are downloaded,
the SIMATIC iMap configuration tool generates an error message to this effect. If a
limit value relating to the number or size of components is exceeded, the CPU will
not change to RUN!
Table 5-6
Characteristic Data for PROFINET CBA Communication
Characteristic
Typical value
Limit value
with FB88
with FB90
PROFINET CBA
Number of remote interconnection
partners
32
64
Total of all I/Os
600
600
Data length of all incoming I/Os
3200 bytes
8192 bytes
1452 bytes
Data length of all outgoing I/Os
3200 bytes
8192 bytes
1452 bytes
Data length for arrays and structures
(acyclic interconnections), maximum
2048 bytes
8192 bytes
1452 bytes
Data length for arrays and structures
(cyclic interconnections), maximum
450 bytes
450 bytes
450 bytes
Data length for arrays and structures
(local interconnections), maximum
−
2400 bytes
1452 bytes
Remote interconnections with acyclic transmission
Sampling frequency: sampling interval,
min.
Possible values: 100, 200, 500, and
1000 ms
Fast value: 20%
Medium value: 40%
Slow value: 40%
100 ms minimum
Number of incoming interconnections
64
150 maximum
Number of outgoing interconnections
64
150 maximum
Data length of all incoming
interconnections
2048 bytes
8192 bytes
1452 bytes
Data length of all outgoing
interconnections
2048 bytes
8192 bytes