Performance data and behavior in operation
5.3 Characteristic data of the DP interface / DP slave
CP 342-5 / CP 342-5 FO
Manual, 10/2011, C79000-G8976-C146-09
25
Execution times of the program blocks for PROFIBUS DP
The following table will help you to calculate the CPU cycle times (OB1) in DP master mode.
The table contains the execution time of the program blocks (DP_SEND, DP_RECV)
required for DP processing on the S7-300 / C7-300 CPU.
Component
Explanation / guideline values
Execution time on the CPU
314C-2DP (6ES7 314-6CF00-
0AB0)
Per DP_Send block call:
<3.0 ms at 8 bytes
<5.0 ms at 2160 bytes
1)
Per DP_RECV block call:
<3.3 ms at 8 bytes
<5.8 ms at 2160 bytes
1)
Execution time on the CPU 317-
2PN/DP (6ES7 317-2EJ10-
0AB0)
Per DP_SEND block call:
<1.5 ms at 8 bytes
<2.3 ms at 2160 bytes
1)
Per DP_RECV block call:
<1.7 ms at 8 bytes
<2.8 ms at 2160 bytes 1)
1)
the following applies at data lengths > 240 bytes: The data is transferred segmented over several
block calls.
NOTICE
Time values are guidelines
The times shown for DP master mode should only be considered as guideline values. The
values apply only for a mono master configuration when no other services (for example PG
functions) are processed on the CP.
NOTICE
DP master mode and S7 slaves (ET-200)
You will find important information on using and configuring (importing the GSD file) S7
slaves (ET200) when operating the CP as DP master on the Internet under the following
entry ID:
21628502 (
5.3
Characteristic data of the DP interface / DP slave
General characteristic data
The following characteristic data is important for successful data transfer from the DP master
to the DP slave:
Characteristic
Explanation / values
Depending on the CP type, use the following GSD files:
Generic station
description (GSD)
CP 342-5 (6GK7 342-5DA02-0XE0)
SIEM80D6.GSD
Содержание CP 342-5
Страница 6: ...Product overview and notes CP 342 5 CP 342 5 FO 6 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 14: ...Requirements for use 2 3 Programming CP 342 5 CP 342 5 FO 14 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 22: ...Displays and operator controls 4 2 Mode selector CP 342 5 CP 342 5 FO 22 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 50: ...References B 3 On programming CP 342 5 CP 342 5 FO 50 Manual 10 2011 C79000 G8976 C146 09 ...