Input X2
Parameter
BACnet object
Selection for X2
X2Sel,
STR_VIEW,55
Selection
BACnet object
R/W
Signal type
Range
None
-
-
-
Exhaust air fan speed feedback
pulse
FanEhSpdFb
R
0…300Hz
0…100 %
Exhaust air fan speed feedback
voltage
FanEhSpdFb
R
0…10V
0…100 %
Extract air quality
AQualEx
R
0…10V
0…2000 ppm
Relative humidity for extract air
HuRelEx
R
0…10V
0…100 %
Particulate matter in room
PmR
R
0…10V
0…500 µg/m3
Input X3
Parameter
BACnet object
Selection for X3
X3Sel,
STR_VIEW,57
Selection
BACnet object
R/W
Signal type
Note
None
-
-
-
Extract air quality
AQualEx
R
0…10V
0…2000 ppm
Relative humidity for extract air
HuRelEx
R
0…10V
0…100 %
Particulate matter in room
PmR
R
0…10V
0…500 µg/m3
Rapid ventilation input
RpdVntIn
R
Contact
NO
Kitchen hood ventilation input
KtchVntIn
R
Contact
NO
Fireplace ventilation input
FplcVntIn
R
Contact
NO
Air filter differential pressure
monitor
FilAirDiffPMon
R
Contact
NO
Fire damper feedback
FdpFb
R
Contact
NO
Preheating coil overtemperature
detector
PreHclOvrTDet
R
Contact
NC
Heat exchanger condensation
monitor
HExgCdnMon
R
Contact
NO
Rotary heat exchanger fault
RotHExgFlt
R
Contact
NO
Heat exchanger differential
pressure monitor
HExgDiffPMon
R
Contact
NO
Heating coil overtemperature
detector
HclOvrTDet
R
Contact
NC
Cooling coil DX evaporator fault
CclDxFlt
R
Contact
NO
Emergency off
EmgOff
R
Contact
NC
Smoke extraction
Smext
R
Contact
NO
Input room operating mode comfort CmfOpModRIn
R
Contact
NO
Input room operating mode
economy
EcoOpModRIn
R
Contact
NO
Input room operating mode
unoccupied
UcdOpModRin
R
Contact
NO
Input room operating mode
protection
PrtOpModRIn
R
Contact
NO
Configuration
Configuring the hardware
4
38 | 170
A6V10733786_en_c