6.2.5 Ebm-papst exhaust air fan
Slave address: 2
Notes
●
The fan configuration must be set with ebm-papst tool "EC Control"
●
The configuration depends on the specific use case
●
The following settings are required or recommended
Setting
Parameter
Value
Communication parameters
Device address (required)
1
Communication speed (required)
19200
Communication parity (required)
8E
Device status
Source of set value (required)
RS485/Bus
Save set value to EEPROM (required)
No
Fail-safe function
Fail-safe mode (recommended)
Fail safe speed value
Set fail safe speed % (recommended)
0
For additional information please refer to the manufacturer’s web site
.
You can contact a local representative, access downloads and get more technical
information for the fan.
BACnet object / device register assignment
Actual I/O
values
BA-objects
R/W
Note
Register
Address
Function code
Exhaust air fan
speed
FanEhSpd
AO,150
RW
53250
06: Write single
Exhaust air fan
fault
FanEhFlt
BI,145
R
53266
04: Read input
Bit 4
Exhaust air fan
speed
feedback
FanEhSpdFb
AI,164
R
53265
04: Read input
Exhaust air fan
total operating
hours
FanEhTotOph
AI,162
R
53258
03: Read
holding
I/O reliability & control
BA-object
R/W
Note
Register
address
Function code
Polling /
heartbeat / COV
Exhaust fan error code
FanEhErrCode
AVAL,688
R
0: No error
> 0: see ebm-papst
53266
04: Read input
Exhaust fan warning code
FanEhWrnCode
AVAL,689
R
0: No error
> 0: see ebm-papst
53267
4: Read inpu
Exhaust fan reset
FanEhRst
BO,103
RW
Pulse, executed by
acknowledge or reset
53249
06: Write single
Bit 0
Engineering of communicative devices
Modbus components
6
152 | 170