Siemens Climatix POL822 Скачать руководство пользователя страница 7

7 / 12 

Siemens room unit QAA822 

 

   

 

Building Technologies 

The  button  locking  is  used  to  protect  the  setting  from  the 
unauthorized  intervention  by  a  non-instructed  person.  The  lock  is 

activated  by  pressing  and  holding  the  button 

Occupancy 

(for 

approx.  8s).  The  lock  is  indicated  on  the  display  by  the  notice 

“LOCK“

.  In  this  condition,  no  changes  of  values  or  modes  are 

possible.  When  you  press  any  button  on  the  display,  the  notice 

“LOCK“ 

occurs on

 

the

 

display. The buttons are unlocked again by 

pressing  and  holding  the  button 

Occupancy. 

The  unlocking  is 

indicated on the display by the notice 

“OPEN“

.  

 
 

The  room  unit  can  be  reset  by  pressing  and  holding  the  button 

Fan

 

(approx.8s). Upon pressing this button, the display goes out and new 

initialization is started and the communication is resumed.  

 
 

The correct system time setting is necessary for the correct function 
of  the  air  conditioning  unit  according  to  the  time  schedule.  The 

system time setting is activated by pressing and holding the button 

Parameters. 

The  time  can  be  changed  by  the 

Plus

  or 

Minus 

buttons and confirmed by the 

Info

 button.   The setting  sequence 

of  the  values  of  the  system  time  changes  in  cycles  and  is  as 
follows:   

Hour  →  minutes→  time  format  →year→  month  →  day  → 
hour… 

The  setting  is  quitted  by  pressing  the  button 

Parameters

  or  after 

inactivity exceeding 30s. 
The  system  time  can  also  be  set  on  the  control  panel  of  the 
Climatic  controller  or  through  the  web  viewer  of  the  computer 
connected  to  the  Climatix  controller  in  the  OS-designated 
switchboard. The system time setting is described in the document 
„Detailed instructions for control through HMI Climatix“. 
 

 

The  parameters  of  the  Climatix  controller  are  factory-preset  so  that 
communication is established as soon as the room unit is connected 

to  the  controller.  The  parameter  initialization  is  indicated  on  the 
display by the letter 

P-

. The communication parameters can be set 

both on the Climatix controller and the room unit. When two room 
units are used, it is necessary to change the parameter 

007

 in one 

of  the  room  units.    The  access  code  is  „0000“  and  is  preset.  The 
communication parameter can be changed as follows:  
Press  the  buttons 

OFF/ON

Mode

Plus 

and 

Minus 

at  the  same 

time to activate the entry of the four-digit access code. The cursor 
is blinking at the first position and by repeated pressing the 

Mode 

button the first flashing parameter

 001 

is displayed. Using the 

Plus 

and 

Minus

  buttons  select  the  flashing  parameter  to  be  changed 

and  confirm  the  setting  by  the 

Mode 

button.  The  cursor  jumps  to 

the  value  below,  which  can  be  also  changed  by 

Plus 

and 

Minus 

buttons. The setting is again confirmed by the 

Mode 

button and the 

setting  of  all  communication  parameters  is  quitted  by  repeated 
pressing the 

OFF/ON 

button. 

 
 

Button locking 

Room unit reset 

System time 

Communication 

Содержание Climatix POL822

Страница 1: ......

Страница 2: ...oard and a room temperature sensor an LCD panel and key buttons for selection of operating mode temperature set up time setting and fan speed The rear cover includes terminal connections for connection of two wire communication conductors Both covers are made of plastic material The cover removal is described in the Installation manual that forms a part of the package Control buttons and display C...

Страница 3: ...4 Operation with the use of power saving function of energy recovery and air mixing The flashing icon indicates the failure of generator energy saving function 15 Failure indication The flashing icon indicates a new failure The lighting icon indicates an extinct failure not confirmed quitted by the operator or a failure that has been quit by the operator but has not extinguished yet Further detail...

Страница 4: ...indicated on the display by the combination of the relevant icons 6 7 and 8 In the mode Economy the air conditioning unit is heating or cooling so that the temperature required for this Economy mode is reached This mode is indicated on the display by the icon 7 The default setting for this mode is 18 C The current temperature can be changed temporarily by the Plus or Minus buttons The temperature ...

Страница 5: ...chedule by the button Fans in six steps within the speed ranges preset for the modes Economy and Comfort if the configuration parameters enable to control the speed from the room unit Temperatures for the modes Economy and Comfort controlled according to the time schedule cannot be changed from the room unit as they are also controlled according to the time schedule or configuration parameters The...

Страница 6: ... temperature C Ven outdoor temperature C VoT temperature of heating water on the return pipe C VoC temperature of the cooling water on the return pipe C Spa temperature of the waste gases of gas heating C Odv temperature of exhaust air C Rek temperature behind the recuperator C Chl temperature behind the cooler C Ohr temperature behind the heater C Vlh air humidity Kval air quality The information...

Страница 7: ... exceeding 30s The system time can also be set on the control panel of the Climatic controller or through the web viewer of the computer connected to the Climatix controller in the OS designated switchboard The system time setting is described in the document Detailed instructions for control through HMI Climatix The parameters of the Climatix controller are factory preset so that communication is...

Страница 8: ...e is 1 007 Zone address 1 1 X The range is 1 to 15 The preset value is 1 008 Enable the network failure detection Enables or disables the detection of the communication network failure The failure is indicated by a blinking notice NET 009 Automatic assignment of the individual address 0 the room unit uses the defined fixed individual address 1 the room unit generates automatically the individual a...

Страница 9: ...itions for mounting the device must be observed The mounting instructions are enclosed with the device Installation Local installation regulations must be observed The equipment is not protected against accidental connection to AC 230 V Commissioning After interruption of the connection to the 2 wire interface the communication is re established only if the room units send a query about the contro...

Страница 10: ...e room unit 2 wire interface connection Voltage signal logic 0 5 V Voltage signal logic 1 7 V Maximum number of controllers 8 Baud rate 4 8 kbps Cable connection Connection terminals screw terminals Solid or stranded conductors 0 8 2 5 mm2 Cable type 2 wire twisted pair unshielded Max distance between two units 75 m Max total busbar length 125 m Degree of cover protection Protection according to E...

Страница 11: ...ilding Technologies Make yourself familiar with the requirements for CE marking as defined in the EMC directive 2004 108 EC Dimensions See Dimensions Colour Front cover rear cover buttons RAL9003 white Weight Without packaging 0 12 kg ...

Страница 12: ...al layout Dimensions units mm Connection of the room unit to the Climatix controller Room unit 1 Room unit 2 Climatix controller Process Bus 2 wire interface power supply device power supply data positive device power supply data negative Negative Positive 3982Z07 3982M01 3982M02 ...

Отзывы: