Complementary  modes  are  activated  when  the  operating  modes 

Comfort

  and 

Economy

  are  deactivated.  Upon  activation  of  the 

complementary  mode,  the  air  conditioning  unit  is  switched  on  so 
that  the  quality  of  the  air  conditioning  unit  operation  is  improved 
with  regard  to  the  conditioned  room,  i.e.  to  avoid  unnecessary 
cooling  down  or  overeating  of  the  conditioned  room  in  the  period 
when  the  operating  modes 

Economy

  and 

Comfort

  are 

deactivated.  The  complementary  modes  can  also  function  as 
protection  of  the  equipment  and  the  conditioned  room.  These 
complementary  modes  are  activated  in  the  configuration 
parameters

*)

 

 

The selection of 

Time Schedule

 is indicated on the display by the 

icon  6.  When  you  select  this  mode,  so  the  controller  switches 
between the  modes according to the time schedule adjusted. The 
modes 

Economy

 and 

Comfort

 are again indicated by the icons 7 

and  8  together  with  the  icon  6.  The  switched-off  modes 
(complementary  frost  protection  mode)  are  indicated  by  icon  6 
only. 
Temporary  change  of  the  modes  in  the  time  schedule  can  be 
performed  by  the 

Occupancy

  button

The  temporary  change  is 

indicated  by  the  flashing  icon  6  and  the  icon  of  the  active  mode. 
This temporary change will last until the next change of the mode 
according to the time schedule. 
The fan speed can be changed in the time schedule by the button 

Fans 

in  six  steps  within  the  speed  ranges  preset  for  the  modes 

Economy 

and 

Comfort,

 if the configuration parameters enable to 

control the speed from the room unit.  
Temperatures  for  the  modes 

Economy 

and 

Comfort 

controlled 

according to the time schedule cannot be changed from the room 
unit  as  they  are also  controlled  according  to  the  time  schedule  or 
configuration parameters

*)

.  

The  time  schedule  can  be  programmed  for  the  whole  year.  The 
individual points of the time schedule are set on the control panel 
of the Climatix controller or through the web viewer of the computer 
connected  to  the  Climatix  controller  in  the  OS-designated 
switchboard.  The  time  schedule  setting  is  described  in  the 
document „Detailed instruction for control through HMI Climatix“. 

Description of individual functions 

There  are  two  ways  to  set  up  the  temperatures  required  for  the 

Comfort

  mode  outside  the  time  schedule  (only  the  icon  8  is  on). 

Temporary  temperature  setting,  until  the  next  change  of  mode,  or 

permanent temperature setting. The temporary temperature setting 
is made by the buttons 

Plus

 or 

Minus 

when the

 Comfort 

mode is 

active.

 

To  set  the  temperature  permanently,  press  the  button 

Parameters, 

an image with  the parameter 

Comf

 and the flashing 

required temperature for the 

Comfort 

mode are displayed. Change 

the  temperature  to  the  required  value  using  the 

Plus

  or 

Minus

 

buttons.  The  setting  is  quitted  by  the 

Info

  button  or  automatically 

after 30 seconds of inactivity.  
 

Complementary modes 

Time schedule 

Setting the required 
temperature for 

Comfort

 mode  

Содержание Climatix POL822

Страница 1: ......

Страница 2: ...oard and a room temperature sensor an LCD panel and key buttons for selection of operating mode temperature set up time setting and fan speed The rear cover includes terminal connections for connection of two wire communication conductors Both covers are made of plastic material The cover removal is described in the Installation manual that forms a part of the package Control buttons and display C...

Страница 3: ...4 Operation with the use of power saving function of energy recovery and air mixing The flashing icon indicates the failure of generator energy saving function 15 Failure indication The flashing icon indicates a new failure The lighting icon indicates an extinct failure not confirmed quitted by the operator or a failure that has been quit by the operator but has not extinguished yet Further detail...

Страница 4: ...indicated on the display by the combination of the relevant icons 6 7 and 8 In the mode Economy the air conditioning unit is heating or cooling so that the temperature required for this Economy mode is reached This mode is indicated on the display by the icon 7 The default setting for this mode is 18 C The current temperature can be changed temporarily by the Plus or Minus buttons The temperature ...

Страница 5: ...chedule by the button Fans in six steps within the speed ranges preset for the modes Economy and Comfort if the configuration parameters enable to control the speed from the room unit Temperatures for the modes Economy and Comfort controlled according to the time schedule cannot be changed from the room unit as they are also controlled according to the time schedule or configuration parameters The...

Страница 6: ... temperature C Ven outdoor temperature C VoT temperature of heating water on the return pipe C VoC temperature of the cooling water on the return pipe C Spa temperature of the waste gases of gas heating C Odv temperature of exhaust air C Rek temperature behind the recuperator C Chl temperature behind the cooler C Ohr temperature behind the heater C Vlh air humidity Kval air quality The information...

Страница 7: ... exceeding 30s The system time can also be set on the control panel of the Climatic controller or through the web viewer of the computer connected to the Climatix controller in the OS designated switchboard The system time setting is described in the document Detailed instructions for control through HMI Climatix The parameters of the Climatix controller are factory preset so that communication is...

Страница 8: ...e is 1 007 Zone address 1 1 X The range is 1 to 15 The preset value is 1 008 Enable the network failure detection Enables or disables the detection of the communication network failure The failure is indicated by a blinking notice NET 009 Automatic assignment of the individual address 0 the room unit uses the defined fixed individual address 1 the room unit generates automatically the individual a...

Страница 9: ...itions for mounting the device must be observed The mounting instructions are enclosed with the device Installation Local installation regulations must be observed The equipment is not protected against accidental connection to AC 230 V Commissioning After interruption of the connection to the 2 wire interface the communication is re established only if the room units send a query about the contro...

Страница 10: ...e room unit 2 wire interface connection Voltage signal logic 0 5 V Voltage signal logic 1 7 V Maximum number of controllers 8 Baud rate 4 8 kbps Cable connection Connection terminals screw terminals Solid or stranded conductors 0 8 2 5 mm2 Cable type 2 wire twisted pair unshielded Max distance between two units 75 m Max total busbar length 125 m Degree of cover protection Protection according to E...

Страница 11: ...ilding Technologies Make yourself familiar with the requirements for CE marking as defined in the EMC directive 2004 108 EC Dimensions See Dimensions Colour Front cover rear cover buttons RAL9003 white Weight Without packaging 0 12 kg ...

Страница 12: ...al layout Dimensions units mm Connection of the room unit to the Climatix controller Room unit 1 Room unit 2 Climatix controller Process Bus 2 wire interface power supply device power supply data positive device power supply data negative Negative Positive 3982Z07 3982M01 3982M02 ...

Отзывы: