Siemens room unit QAA822 

 

   

 

Building Technologies 

Use 

The room unit is intended for basic users control and monitoring of 
the function of Mandík air conditioning units incl. basic parameters.  
The measurement of temperature of the room, where the room unit 
is installed, is integrated. Up to two room units can be connected to 
the Mandík measurement and control system. The room unit is not 
intended  for  setting  the  configuration  parameters.    The 
configuration  parameters  are  set  on  the  control  panel  of  Climatic 
controller or through the web viewer of the computer connected to 
the  Climatix  controller  installed  in  the  switchboard  with  OS 
designation.  The  parameter  setting  is  described  in  the  document 
„Detailed instruction for control through HMI Climatix“. 

Characteristics

 

The room unit is intended for semi-flushed surface mounting with a 
recessed installation box. The cable entry is through the rear of the 
unit.  
The unit consists of a front cover with electronics and a rear cover. 
The rear cover can be removed after loosening the safety 
mechanism. 
The front cover comprises a printed-circuit board and a room 
temperature sensor, an LCD panel and key buttons for selection of 
operating mode, temperature set-up, time setting and fan speed. 
The rear cover includes terminal connections for connection of two-
wire  communication  conductors.  Both  covers  are  made  of  plastic 
material.  

 

The cover removal is described in the Installation manual that 
forms a part of the package.  

Control buttons and display 

Cover removal 

No. 

Icon 

Name 

Function 

 

ON/OFF

 

Button for switching on or off the air conditioning 
unit. 

 

Occupancy

 

The button enables to switch on/off temporarily the 
occupancy mode in the time programme.  

 

Parameters 

The button enables to change the required 
temperature values or to quit the viewing of the 
actual temperatures. 

 

Minus

 

The button for changing the set-point of the selected 
parameter or temperature. 

 

Plus

 

The button for changing the set-point of the selected 
parameter or temperature. 

 

Info

 

By pressing the button the viewing of current 
temperatures is activated or the possibility to change 
the required temperatures is quitted.  

 

Fan

 

The button is used to set the fan speed within the 
pre-set fan speeds for the modes 

Economy 

and 

Comfort

 

Mode

 

Using this button you can switch between the modes 

Time Schedule, Economy and Comfort

, when the 

air conditioning unit is on. 

Buttons

 

Содержание Climatix POL822

Страница 1: ......

Страница 2: ...oard and a room temperature sensor an LCD panel and key buttons for selection of operating mode temperature set up time setting and fan speed The rear cover includes terminal connections for connection of two wire communication conductors Both covers are made of plastic material The cover removal is described in the Installation manual that forms a part of the package Control buttons and display C...

Страница 3: ...4 Operation with the use of power saving function of energy recovery and air mixing The flashing icon indicates the failure of generator energy saving function 15 Failure indication The flashing icon indicates a new failure The lighting icon indicates an extinct failure not confirmed quitted by the operator or a failure that has been quit by the operator but has not extinguished yet Further detail...

Страница 4: ...indicated on the display by the combination of the relevant icons 6 7 and 8 In the mode Economy the air conditioning unit is heating or cooling so that the temperature required for this Economy mode is reached This mode is indicated on the display by the icon 7 The default setting for this mode is 18 C The current temperature can be changed temporarily by the Plus or Minus buttons The temperature ...

Страница 5: ...chedule by the button Fans in six steps within the speed ranges preset for the modes Economy and Comfort if the configuration parameters enable to control the speed from the room unit Temperatures for the modes Economy and Comfort controlled according to the time schedule cannot be changed from the room unit as they are also controlled according to the time schedule or configuration parameters The...

Страница 6: ... temperature C Ven outdoor temperature C VoT temperature of heating water on the return pipe C VoC temperature of the cooling water on the return pipe C Spa temperature of the waste gases of gas heating C Odv temperature of exhaust air C Rek temperature behind the recuperator C Chl temperature behind the cooler C Ohr temperature behind the heater C Vlh air humidity Kval air quality The information...

Страница 7: ... exceeding 30s The system time can also be set on the control panel of the Climatic controller or through the web viewer of the computer connected to the Climatix controller in the OS designated switchboard The system time setting is described in the document Detailed instructions for control through HMI Climatix The parameters of the Climatix controller are factory preset so that communication is...

Страница 8: ...e is 1 007 Zone address 1 1 X The range is 1 to 15 The preset value is 1 008 Enable the network failure detection Enables or disables the detection of the communication network failure The failure is indicated by a blinking notice NET 009 Automatic assignment of the individual address 0 the room unit uses the defined fixed individual address 1 the room unit generates automatically the individual a...

Страница 9: ...itions for mounting the device must be observed The mounting instructions are enclosed with the device Installation Local installation regulations must be observed The equipment is not protected against accidental connection to AC 230 V Commissioning After interruption of the connection to the 2 wire interface the communication is re established only if the room units send a query about the contro...

Страница 10: ...e room unit 2 wire interface connection Voltage signal logic 0 5 V Voltage signal logic 1 7 V Maximum number of controllers 8 Baud rate 4 8 kbps Cable connection Connection terminals screw terminals Solid or stranded conductors 0 8 2 5 mm2 Cable type 2 wire twisted pair unshielded Max distance between two units 75 m Max total busbar length 125 m Degree of cover protection Protection according to E...

Страница 11: ...ilding Technologies Make yourself familiar with the requirements for CE marking as defined in the EMC directive 2004 108 EC Dimensions See Dimensions Colour Front cover rear cover buttons RAL9003 white Weight Without packaging 0 12 kg ...

Страница 12: ...al layout Dimensions units mm Connection of the room unit to the Climatix controller Room unit 1 Room unit 2 Climatix controller Process Bus 2 wire interface power supply device power supply data positive device power supply data negative Negative Positive 3982Z07 3982M01 3982M02 ...

Отзывы: