e1276e
5
Siemens Building T
echnologies
Cerberus Division
09.2000
2.3
General data
Value
Parameters
Symbol
Unit
min.
typ.
max.
Conditions
Distance between detector and
reflector
Additional area
(without approval)
L
m
8
5
100
8
<10m filter DLF1191-AA
Filter DLF1191-AB
Response sensitivity
reduced
standard
increased
D
1
%
%
%
65
50
30
Attenuation of the beam
(forward and return path)
Compensation (if beam is
attenuated)
Compensation speed
%
%/h
50
4
Self-test interval
min.
15
Alarm integration
s
6
16
Dependent on diagnosis
Fault activation
%
>90
Attenuation of the beam
IR transmitter
Wavelength
Pulse frequency
Pulse length
nm
Hz
µ
s
880
6
25
Attenuation of the beam
Elektromagnetic compatibility
V/m
50
1MHz...1GHz
Operating temperature
T
a
°
C
–25
+60
Humidity
≤
30
°
C
>30
°
C
≤
95% rel.
≤
29g/m
3
Storage temperature
T
l
°
C
–30
+75
Colour: pure white
~RAL9010
Detector heater DLR1191 / DLH1191
Supply voltage
U
H
V
DC
20
30
Operating current
I
H
mA
33
50
Resistance
R
Ω
600
Classification
Standards
BS 5839: Part 5
CE conformity marking
Application category
IEC 721-3:
3K6
Test category
IEC 68-1:
25/060/42
Protection category
EN60529 / IEC529: IP65
Compatibility
To AlgoRex interactive fire detection system with AlgoLogic S11
To Cerberus control units with collective detector evaluation
Environmental compatibility:
Easy to overhaul
Easy to uninstall and disassemble
Plastic material identifiable through embossed code