e1276e
32
Siemens Building T
echnologies
Cerberus Division
09.2000
6
Commissioning
6.1
Settings
Remove the detector cover
Set the DIP switches
The DLO1191 can be operated either on an interactive DS11 line or a collective line. The
choice between collective and interactive line is made with DIP switch [S4].
The detector has 3 sensitivity settings («Reduced», «Standard», «Increased»). The re-
sponse threshold is set with DIP switch [S1], [S2].
The transmitter intensity (strong, weak) can be set with DIP switch [S3].
The DIP switch [S3] which governs the transmitter intensity is set to «strong» by default. If
the signal amplitude is too high (display on the adjustment unit: Range = 13, signal > 50),
the transmitter can be set to «weak». If the measurement section is
≤
10m, a supplemen-
tary filter must be installed.
Function
S1
S2
S3
S4
S5
S6
Reduced sensitivity
##
##
##
OFF
##
##
##
ON
Standard sensitivity
##
##
##
ON
OFF
##
##
##
ON
OFF
Increased sensitivity
##
##
ON
##
##
OFF
Weak transmitter signal
###
###
ON
Strong transmitter signal
###
###
OFF
Collective system
##
##
##
ON
Interactive system
##
##
OFF
Reserve
##
##
«S6 ON»
Alarm at beam interruption
(< 60s)
##
##
ON
*
«S6 OFF»
Fault at beam interruption
(< 30s)
##
##
##
OFF
* Operating conditions according to BS 5839: Part 5
Fig. 33 Settings