BANY Agent 

 

29 

Compact Operating Instruction 

 

5.4  Digital In/Outputs 

 

The digital Inputs and Outputs are floating switches by breaking the contact. 

 

Connecting the digital In/Outputs 

 

The digital In/Outputs contacts are connected to a 4-pin plug-in terminal block. 
The digital In/Outputs can be subjected to a maximum load of 50 mA (safety extra low 
voltage SRLV  24 VDC). 
 
 
 
Pin number 

Assignment (24 VDC)  

Labeling 

DI/DO 

In/Output 24 V DC 

 

 

SGND 

Ground for In/Output 

 

SGND 

In/Output 24 V DC 

 

DIDO 

Ground for In/Output 

 

 
 

 

5.5  Connecting functional ground 

 

Installation on a DIN rail 

 

The device is grounded over the DIN rail. 

 

S7 standard rail 

 

The device is grounded over the rear panel and the neck of the screw. 

 

Wall mounting 

 

The device is grounded by the securing screw in the unpainted hole.. 
 
Please note that the BANY Agent must be grounded over one securing screw with 
minimum resistance. 
 
If an BANY Agent is mounted on a non-conducting base, a grounding cable must be 
installed. The grounding cable is not supplied with the device. Connect the paint-free 
surface of the BANY Agent to the nearest grounding point using the grounding cable. 
 

 
 
 

 

Содержание BANY Agent

Страница 1: ...BANY Agent 1 Compact Operating Instruction SIEMENS BANY Agent Compact Operating Instructions ...

Страница 2: ...per precautions are not taken WARNING Indicates that death ore severe personal injury may result if proper precautions are not taken CAUTION With a safety alert symbol indicates that minor personal injury can result if proper precautions are not taken CAUTION Without a safety alert symbol indicates that property damage can result if proper precautions are not taken NOTICE Indicates that an uninten...

Страница 3: ...e must be recommended or approved by Siemens Proper transport storage installation assembly commissioning operation and maintenance are required to ensure that the products operate safely and without any problem The permissible ambient conditions must be complied with The information in the relevant documentation must be observed Trademarks All names identified by R are registered trademarks of Si...

Страница 4: ...1 3 3 Product group BANY Agent 12 3 3 1 BANY Agent with TAP 12 3 3 2 BANY Agent without TAP 14 3 4 Real Time Ethernet Ports TAP A TAP B 16 3 5 Ethernet Ports Network N1 und N2 17 3 6 Ethernet Ports Network P1 und P2 17 3 7 Control Port 17 3 8 USB Host 17 3 9 Micro SD Karte 18 3 9 1 Position of the Micro SD Memory Card 18 3 10 Digital I O 19 3 11 Description of the LEDs 20 3 12 The Buttom 20 4 Asse...

Страница 5: ...nal ground 29 6 Technical data 30 6 1 Construction installation and environmental conditions 30 6 2 Connectors and electrical data 31 6 3 Cable lengths 33 6 4 Other properties 34 7 Dimension drawings 35 7 1 BANY Agent with TAP 35 7 2 BANY Agent without TAP 38 8 Approvals 41 8 1 BANY Agent approvals certificates 41 8 2 BANY Agent Conformity certificates 44 8 3 Overview of BANY Agent approvals 45 8 ...

Страница 6: ... Terms used Product line For all devices and variants of all product groups within the BANY Agent product line the term BANY Agent is used BANY Product group For all devices and variants of a product group only the product group is used Agent Device For a device only the device name is used BANY Agent Variant For a variant of the device the device name has the appropriate variant added to it in br...

Страница 7: ...umber BANY Agent BANY Agent with TAP 9AE4140 1BA01 BANY Agent BANY Agent without TAP 9AE4140 1BA00 1 3 Type designations Structure oft he type designation The type designation of an BANY Agent is made up of several parts that have the following meaning 9AE4140 1BA01 BANY Agent with TAP 9AE4140 1BA02 BANY Agent without TAP ...

Страница 8: ...that only SELV LPS Limited Power Source complying with IEC 60950 1 EN60950 1 VDE 0805 1 must be connected to the power supply terminals The power supply unit for the equipment power supply must comply with NEC Class 2 as described by the National Electrical Code ANSI NFPA 70 There is an additional requirement if devices are operated with a redundant power supply If the equipment is connected to a ...

Страница 9: ...ive 94 9 ATEX95 this enclosure must meet the requirements of at least IP54 in compliance with EN 60529 WARNING Suitable cables for temperatures in excess of 70 C In the cable or conduit entry point exceeds 70 C or the branching point of conductors exeeds 80 C special precautions must be taken If the equipment is operated in an air ambient in excess of 50 C only use cables with admitted maximum ope...

Страница 10: ...NNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON HAZARDOUS WARNING Restricted area of application This equipment is suitable for use in Class I Division 2 Groups A B C and D or non hazardous locations only WARNING Restricted area of application This equipment is suitable for use in Class I Zone 2 Group IIC or non hazardous locations only ...

Страница 11: ...mage WARNING Do not use any parts that show evidence of damage 3 2 BANY Agent components of the product Note When shipped the slots for the media modules have a dummy cover fitted Device BANY Agent Variant Plug in terminal block Device BAK Product CD Digital I O Power supply BANY Agent with TAP 4 pin 4 pin x x x BANY Agent wthout TAP 4 pin 2 pin power supply 2 pin digital I O x x x ...

Страница 12: ...le attachments 7 electrical Ethernet RJ45 jacks with securing collar for connection of end devices or other network segments 1 USB Master connector 1 plug in terminal block 4 pin for connecting the power supply and the digital in Outputs 1 plug in terminal block 4 pin for connecting the digital in Outputs ...

Страница 13: ...BANY Agent 13 Compact Operating Instruction Bild 1 BANY Agent mit TAP ...

Страница 14: ...ent without TAP Possible attachments 3 electrical Ethernet RJ45 jacks with securing collar for connection of end devices or other network segments 1 USB Master connector 1 plug in terminal block 4 pin for connecting the power supply and the digital In Outputs ...

Страница 15: ...BANY Agent 15 Compact Operating Instruction ...

Страница 16: ...ets A1 A2 and B1 B2 are internally connected to a TAP each The ethernet frames are forwarded from one TAP port to the other without delay This also works if the Bany Agent is powered off It is not possible for the Bany Agent to send packets out of the TAP ports Connect networks to be analyzed here Link speed is 100 Mbit s TAP A is deactivated if a cable is plugged to N1 or N2 ...

Страница 17: ...hese ports are used for recording and sending Ethernet or PNIO data Fast Ethernet and Gigabit Ethernet is supported 3 7 Control Port Ctrl RJ45 Ethernet Port connect the Bany Agent to a PC via this port 3 8 USB Host The hardware contains one USB host port Mass storage devices can be connected here The standards USB 1 1 und USB 2 0 are supported The USB interface provide a power supply for connected...

Страница 18: ...orted with a maximum capacity of 32 GB 3 9 1 Position of the Micro SD Memory Card CAUTION The Micro SD memory card is only for internal use and special debug and update functions The Micro SD memory card should not be removed or inserted by the user In the BANY Agent the Micro SD memory card is located behind the sealing screw on the rear of the device To remove the sealing screw use a coin or a w...

Страница 19: ...Agent 19 Compact Operating Instruction 3 10 Digital I O The hardware has 3 connectors which can be used as a digital input or a digital output DI DO digitaler Eingang oder digitaler Ausgang SGND Signal Masse ...

Страница 20: ...until the StartUP LED lights up Control CTRL Lights up green if a link to the network has been established Flashes orange at data exchange LEDs for Ethernet ports TA1 2 TB1 2 N1 N2 Lights up green if a 100MBit s link at the network has been detected Flashes orange when data is received LEDs for Ethernet ports P1 P2 Lights up green if a 100MBit s link at the network has been detected Flashes green ...

Страница 21: ...70 C In the cable or conduit entry point exceeds 70 C or the branching point of conductors exceeds 80 C special precautions must be taken If the equipment is operated in an air ambient in excess of 50 C only use cables with admitted maximum operating temperature of at least 80 C CAUTION Provide suitable shade to protect the Bus Analyser against direct sunlight This avoids unnecessary warming of th...

Страница 22: ...UTION If the BANY Agent is liable to be subjected to serve vibration 10 g use an S7 300 standard rail for installation The DIN rail does not provide adequate support if vibration exceeds 10 g WARNING When used in shipbuilding installation on a 35 mm DIN rail is not permitted In ships the 35 mm DIN rail does not provide adequate support Valid only for the appropriately marked devices in the various...

Страница 23: ... then push it in against the rail until it clips into place 2 Fit the connectors for the power supply 3 Fit the connectors for the digital In Outputs 4 Insert the terminal blocks into the sockets on the BANY Agent Removing To remove an BANY Agent from the DIN rail 1 Disconnect all cables from the BANY Agent 2 Release the lower part of the switch away from the DIN rail ...

Страница 24: ...the BANY Agent to the underside of the standard rail 3 Fit the connectors for the power supply 4 Fit the connectors for the signaling contact 5 Insert the terminal blocks into the sockets on the BANY Agent Uninstalling To remove an BANY Agent from the SIMATIC S7 300 standard rail 1 First disconnect all connected cables 2 Loosen the screws on the underside of the S7 standard rail and lift the BANY ...

Страница 25: ...er and 30 mm long 4 screws 3 5 mm diameter and 40 mm long 2 Connect the electrical cable connecting cables 3 Fit the connectors for the digital In Outputs 4 Insert the terminal blocks into the sockets on the BANY Agent Note For more exact dimensions please refer to the section Dimension drawings Note The wall mounting must be capable of supporting at least four times the weight of the BANY Agent ...

Страница 26: ...ant path before you insert a new or replacement device in an operational network A bad configuration or attachment of the Ethernet cables to incorrectly configured ports causes overload in the network and a breakdown in communication 5 2 Power supply general WARNING You can recognize the type of power supply on a warning on the device and the labeling of the connector to the power supply ...

Страница 27: ...wer supplies must meet these requirements The digital In Outputs can be subjected to a maximum load of 50 mA safety extra low voltage SELV DC 24 V Never operate the device with AC voltage or DC voltage higher than 32 V DC CAUTION If the BANY Agent are supplied over long 24 V power supply lines or networks measures are necessary to prevent interference by strong electromagnetic pulses on the supply...

Страница 28: ...lock assignment 4 pin Pinout of the safety extra low voltage SELV Pin number Assignment 24 VDC Labeling DI DO In Output 24 V DC SGND Ground for In Output M Ground power supply L Power 24 V DC To wire up the power connector use a copper cable of category 18 12 AWG or cable with a cross section of 0 75 to 2 5 mm 5 3 2 24 V DC product group BANY Agent 24 V safety extra low voltage overview Product gr...

Страница 29: ... In Output 24 V DC DIDO Ground for In Output 5 5 Connecting functional ground Installation on a DIN rail The device is grounded over the DIN rail S7 standard rail The device is grounded over the rear panel and the neck of the screw Wall mounting The device is grounded by the securing screw in the unpainted hole Please note that the BANY Agent must be grounded over one securing screw with minimum r...

Страница 30: ...versions of the product group 6 1 Construction installation and environmental conditions Construction BANY Agent with TAP BANY Agent without TAP Dimension W x H x D 60 x 125 x 125 mm 40 x 125 x 125 mm Weight 1 400 g 1 100 g Degree of protection IP20 IP20 Installation options Installation options DIN rail S7 300 standard rail Wall Note When used in shipbuilding installation on a 35 mm DIN rail is n...

Страница 31: ...nis horizontal if the device labeling is from left to right With a vertical installation the device labeling is rotated through 90 6 2 Connectors and electrical data Connection for end devices or network components BANY Agent with TAP 24 V DC 7 x RJ45 jacks with MDI X assignment 10 100 1000 Mbit s half full duplex BANY Agent with TAP 24 V DC 1 x USB BANY Agent without TAP 24 V DC 3 x RJ45 jacks wi...

Страница 32: ...sion power supply Voltage via digital In Output Switching capacity resistive load BANY Agent with TAP 24 V DC 24 V DC 50 mA BANY Agent without TAP 24 V DC 24 V DC 50 mA Electrical data USB Port Device version power supply Voltage via USB port Current load maximum BANY Agent with TAP 24 V DC 5 V DC 500 mA BANY Agent without TAP 24 V DC 5 V DC 500 mA Plug in terminal block for connectors of the powe...

Страница 33: ...10m TP Cord 0 75 m 10 m TP Cord Mit IE FC RJ45 Plug 180 0 85 m IE FC TP Standard Cable Mit IE FC Outlet RJ45 10m TP Cord 0 90 m 10 m TP Cord Mit IE FC RJ45 Plug 180 0 100 m Zulässige Leitungslängen Kupferleitung Gigabit Ethernet Leitungstyp Accessory Plug Outlet TP Cord Permitted cable length IE FC Standard Cable 4 x 2 AWG24 IE FC Flexible Cable 4 x 2 AWG24 with IE FC RJ45 Plug 180 4 x 2 0 90 m IE...

Страница 34: ...BANY Agent 34 Compact Operating Instruction 6 4 Other properties Mean Time between failure MTBF MTBF 40 years ...

Страница 35: ...BANY Agent 35 Compact Operating Instruction 7 Dimension drawings 7 1 BANY Agent with TAP ...

Страница 36: ...BANY Agent 36 Compact Operating Instruction ...

Страница 37: ...BANY Agent 37 Compact Operating Instruction ...

Страница 38: ...BANY Agent 38 Compact Operating Instruction 7 2 BANY Agent without TAP ...

Страница 39: ...BANY Agent 39 Compact Operating Instruction ...

Страница 40: ...BANY Agent 40 Compact Operating Instruction ...

Страница 41: ...rective electromagnetic compatibility The SIMATIC NET product meets the requirement of the EC Directive 2004 108 EG electromagnetic compatibility The product is designed for use in the following areas Area of application Requirements Emission Immunity Industrial area EN 61000 6 4 2011 EN 61000 6 2 2005 WARNING Personal injury and damage to property occur The installation of expansions that are not...

Страница 42: ...ers of machines This product is not a machine in the sense of the EC Machinery Directive There is therefore no declaration of conformity relating to the EC Machinery Directive 2006 42 EEC for this product Machinery directive The product is a component in compliance with the EC 2006 42 EG According to the machinery directive we are obliged to point out that the product described is intended solely ...

Страница 43: ...mation Customer Support under the following entry ID 33118441 http support automation siemens com WW view de 33118441 Entry list tab entry type Certificates ATEX Code II 3 G Ex nA II T4 KEMA 07 ATEX 0145X The product meets the requirements oft he standards EN 60079 15 2005 Electrical apparatus for potentially explosive atmospheres Type of protection n Und EN 60079 0 2006 FM approval The product me...

Страница 44: ...C22 2 No 60950 1 03 UL 1604 und UL 2279 or ANSIISA 12 12 01 Approved for use in CI 1 Div 2 GP A B C D T4 CI 1 Zone 2 GP IIC T4 8 2 BANY Agent Conformity certificates Declaration of Conformity You will find the EC Declaration of Conformity for these products on the Internet at the following address http support automation siemens com WW view de 33118441 http support automation siemens com WW view d...

Страница 45: ... T AS NZS 2064 Class A EN 6100 6 4 Class A EN 61000 6 2 EN 60079 15 2005 EN 60079 0 2006 II 3 G Ex nA II T KEMA 07 ATEX 0145X with TAP X X without TAP X x 1 For temperature information T or the maximum ambient temperature Ta refer to the type plate Note Shipbuilding approval No applications for shipbuilding approvals will be made for the BANY Agent 8 4 Mechanical stability in operation BANY Agent ...

Страница 46: ...BANY Agent 46 Compact Operating Instruction ...

Отзывы: