4
3ZX1012-0SF30-0AN1
C
ommissioning
To start up the module, carry out the following steps:
M12 position switch
Status-LEDs
The following table shows the status - LEDs and their operating states:
Technical data
Electrical data as per
AS-i specification
I/O configuration (hex)
0
ID code (hex)
B
Total current drain
I
≤
45 mA
Reverse polarity protection
yes
Inputs
Low sigal range
contact open
High signal range
contact closed
I
in
dynamic (I
peak
≥
5 mA)
Mechanical data
Degree of protection
IP 65 / IP 20 (emergency stop on front panel)
Weight
approx. 30 g
Dimensions in mm (h x w x d)
IP 20
65 x 31 x 50 max (with screw plug, 40 ± 5 Ncm)
IP 65
58 x 31 x 50 max (with screw plug, 40 ± 5 Ncm)
Temperature range
Rated temperature
T
u
25 °C
Ambient temperature
T
a
- 25 °C to 70 °C
Storage temperature
T
s
- 40 °C to 85 °C
Material
Casing
Polycarbonate
NBR for O-ring in the M12 sockets
Approval
cUL
CLASS II ONLY
Fig. 5
Clip
Fig. 6
AS-i cable
Fig. 7
Step 6
100
mm
100
mm
Step
Procedure
1
Set the address if you want to carry out addressing prior to installation.
2
Lay the AS-i cable with the broad side facing downwards (Fig. 5).
3
Fasten the clip to the F adapter in accordance with the code
(the clip code determines the polarity).
4
Fasten the clip and the AS-i cable to the AS-i F adapter (Fig. 6).
5
Set the address if you have not carried out step 1.
6
Caution: Attach strain relief!
(Fig. 7)
7
Mounting the Heavy Duty Fixing
If the 3SF5402-1AA01 ASI-F adapter is to be removed and then later remounted, the enclosed half-
shells must also be mounted (Fig.11).
Notes
• Cover the address jack which is not used with the screw plug, in order to comply with the specified
degree of protection.
• Each code table may occur only once in one AS-i line connected to the safety
monitor.
Fig.11
PRESS
1
2
max. 0,7 Nm
2
3
1
4
Fig. 8
For contact assignment for M12
(Fig. 8, category 4)
Pin 1
Channel 2
Terminal for next position switch
Pin 2
Channel 2
Terminal for next position switch
Pin 3
not used
Pin 4
not used
F- IN 2
F- IN 1
SIEMENS
2FI S0.B
CE
NTERFACE
SAFETY AT WORK
ADDR.
green: AS-I
red: FAULT
AS-i
FAULT
Fig. 9
Fig. 10
AS-i / FAULT
Operating state
(Fig.9)
green
Communication OK
Off
No voltage present at AS-Interface-Chip
red permanent
Communication failed
red/yellow flashing
Slave has address "0"
Channels
Operating state
(Fig. 10)
F - IN1
LED on: contact closed
F - IN2
LED on: contact closed