Instruction manual AQ101, AQ101D, AQ110P, AQ01
34 (48
)
7.1.3
A
UXILIARY VOLTAGE
Us (min-max):
Us (nominal)
85
–
265V AC / DC
110, 220 V DC, 110, 115, 220, 230 V AC 50/60 Hz
18
–
72 V DC
24, 36, 48, 60 V DC
Maximum interruption in normal operating state:
100 ms
Maximum power consumption:
5W (AQ110P)
4W (AQ101, AQ101D)
7.1.4
C
URRENT MEASUREMENT CIRCUITS
IL1-IL3,
I
O
(AQ110P
ONLY
)
Nominal current
1 or 5A
Rated Frequency
2
…
1000Hz
Number of inputs
3 (phase) + 1 (residual)
Thermal withstand continuous
30A
Thermal withstand 1s
500A
Thermal withstand 10s
100A
Phase overcurrent setting range
0.5
…
6 x In
Residual overcurrent setting range
0.05
…
2 x In
Measurement accuracy
10%
Rated AC Burden (VA)
Input resistance <10m
Ω
7.1.5
T
RIP RELAYS
T1,
T2,
T3,
T4
Number
3 NO + 1 NC or 4 NO
Rated voltage
250V ac/dc
Continuous carry
5A AC / DC
Make and carry for 0.5s
30A DC
Make and carry for 3s
16A DC
Breaking capacity DC, when time constant
L/R=40ms
40W (0.36A at 110 V DC)
Contact material
AgNi 90/10