Instruction manual AQ101, AQ101D, AQ110P, AQ01
26 (48
)
Light channel activation
Figure 4-2: Light channel activation.
Light channels are commissioned by applying strong light to the light sensor
detector area. The same procedure applies also for fiber sensors.
1)
Applying light to the sensor.
2)
Corresponding light sensor channel LED lights steadily when light has been
detected.
Use strong, non-LED, light source for light channel activation. Light
sensors are available with different sensitivity levels. Least sensitive
sensors require stronger light source. Refer to sensor ordering codes.
Activation longer than 3s will initiate self-supervision error. Refer to
trouble shooting and LED indications.