background image

GAMMA

instabus

Technical Product-Information

August 2017

Control Module Box AP 118

5WG1 118-4AB01

Technical Manual

AP 118, page 4 / 6

Siemens AG

Infrastructure and Cities Sector, Building Technologies

Update: http://www.siemens.com/gamma

© Siemens AG 2017

Control Products and Systems

Subject to change without further notice.

P. O. Box 10 09 53, D-93009 Regensburg

2.4.2.11/4

Mounting of RS  / RL modules

B1

RS module

B2

RL module

B3

Type label (with space for physical address of the
module)

B4

Mounting location for RS / RL module in AP 118
Control Module Box or AP 641 Room Control Box

B5

Bus connection module with bus connection pins
for bus terminal block, LED for indicating normal
operating mode (LED off) or addressing mode (LED
on), Learning button and contacts to RS module

B6

Insertion point for bus connection module of the RS
module

B7

Snap-in point for bus connection module of the RS
module

B8

Learning button for switching between normal
operating mode and addressing mode and for re-
ceiving the physical address

B9

LED for indicating normal operating mode (LED off)
or addressing mode (LED on); returns to normal op-
erating mode automatically after receiving the phys-
ical address

B10

Bus connection pins of the module for connection
of the bus terminal block in the respective mounting
location

B11

Insertion point for bus terminal

B12

Bus connection block for single core conductors
with 0,6...0,8 mm Ø

B13

Hinge joint for mounting hinge of the RL module

B14

Terminals

Mounting of a RS module:

- AP 118: Remove the lid of the Control Module Box.
-Insert the bus connection module (B5) in such a way

into the insertion point (B6) for the bus connection
module that the  bus connection pins (B10) point to the
insertion point for the bus terminal (B11).

- Press the bus connection module (B5) down until it

snaps into the locking position (B7).

-Insert the RS module (B1) from the top with the termi-

nals (B14) pointing away from the bus terminal inser-
tion point (B11). The type label (B3) is on top.

-Insert the bus terminal (B12) of the mounting location

(B4) onto the bus connection pins (B10) of the bus con-
nection module (B5).

-For assignment of the Physical Address press the learn-

ing button (B8) for a maximum of 2 seconds. The ad-
dressing mode is indicated when the LED is on (B9). It
returns to normal operating mode (LED Off) automati-
cally after receiving the physical address.

- Mount the lid again.

figure 5: mounting of a RS module

Dismounting an RS module:

- AP 118: Remove the lid of the Control Module Box.
- Remove the wiring from the terminals (B14).
- Remove the bus terminal (B12).
- To remove the RS module (B1), insert a screw driver

between the module and the mounting location siding
and push it up to release it from the snap-in hooks. Do
this on both sides.

- Pull the RS module (B1) from the mounting location

(B4).

- If an RL module (B2) shall be inserted into the mounting

location, detach the bus connection module (B5) from
the snap-in point (B7), swivel it up and pull it out of the
insertion point (B6).

Mount the lid again.

Содержание AP 118

Страница 1: ...tuator 2 x 6A 5WG1 525 2AB23 Universal dimmer 1 x 250VA The mounted module is connected to the bus line via a bus terminal block The AP 118 Control Module Box provides wiring space with room for two connectors for PE and N conductors This allows for secure connection of the PE and N con ductors of the cables inserted into the AP 118 Control Module Box For strain relief cables can be secured at the...

Страница 2: ... category according to IEC 60664 1 III Bus safety extra low voltage SELV DC 24 V Environmental specifications Climatic withstand capability EN 50090 2 2 Ambient temperature operating 5 45 C Ambient temperature non op 25 70 C relative humidity non condensing 5 bis 93 CE norm complies with low voltage regulations Mounting and Connecting General description The Control Module Box is designed for on s...

Страница 3: ...separately A14 Clamp for strain relief cut off from base A2 A14 A7 A6 A11 A9 A4 A2 A14 A8 figure 2b Mounting Removing the lid of the Control Module Box Remove the screws A3 securing the lid Pull the latching clamp A4 away from the lid A5 lift the lid up swivel it up and remove it from the hinge A6 Mounting the lid of the Control Module Box Hook the lid A5 into the hinge A6 Push the lid A5 down unt...

Страница 4: ... with 0 6 0 8 mm Ø B13 Hinge joint for mounting hinge of the RL module B14 Terminals Mounting of a RS module AP 118 Remove the lid of the Control Module Box Insert the bus connection module B5 in such a way into the insertion point B6 for the bus connection module that the bus connection pins B10 point to the insertion point for the bus terminal B11 Press the bus connection module B5 down until it...

Страница 5: ...he bus terminal B12 To remove the RL module B2 insert a screw driver between the module and the mounting location on the bus terminal side and push it up to release it from the snap in hooks Swivel the RL module B2 up pull it down out of the hinge B13 and remove it from the mounting location B4 Mount the lid again figure 8 dismounting an RL module Wiring Slipping off on bus connection blocks The b...

Страница 6: ...uits are connected via screwless plug in terminals E1 Remove approx 9 10 mm of insulation from the wire E 1 1 and plug it into the terminal E1 The terminals are designed for connection of two wires allowing to loop through the terminal block Note The maximum permissible terminal load current is 16A Remove wires Press the terminal interlocking of the terminal F1 with a screw driver and remove the w...