figure 6: dismounting an RS module
∂
Mounting of an RL module:
- AP 118: Remove the lid of the Control Module Box.
- Insert the RL module (B2) into the hinge (B13) of the
mounting location (B4). The terminals (B14) point away
from the insertion point for the bus terminal (B11). The
type label (B3) is on top.
- Swivel the RL module (B2) down until it audibly snaps
into the mounting location (B4).
- Insert the bus terminal (B12) of the mounting location
(B4) onto the bus connection pins (B10) of the RL mod-
ule (B2).
- For assignment of the Physical Address press the learn-
ing button (B8) for a maximum of 2 seconds. The ad-
dressing mode is indicated when the LED is on (B9). It
returns to normal operating mode (LED Off) automati-
cally after receiving the physical address.
- Mount the lid again.
figure 7: mounting of an RL module
∂
Dismounting an RL module:
- AP 118: Remove the lid of the Control Module Box.
- Remove the wiring from the terminals (B14).
- Remove the bus terminal (B12).
- To remove the RL module (B2), insert a screw driver
between the module and the mounting location on the
bus terminal side and push it up to release it from the
snap-in hooks.
- Swivel the RL module (B2) up, pull it down out of the
hinge (B13) and remove it from the mounting location
(B4).
- Mount the lid again.
figure 8: dismounting an RL module
Wiring
Slipping off/on bus connection blocks
The bus connection block (C2) is situated on the back of
the actuator (C1).
It consists of two components (C2.1 and C2.2) with four
terminal contacts each. Take care not to damage the two
test sockets (C2.3) by accidentally connecting them to
the bus cable or with the screw driver (e.g. when at-
tempting to unplug the bus connection block).
Slipping off bus connection blocks
- Carefully put the screw driver to the wire insertion slit
of the bus connection block’s grey component (C2.2)
and
- pull the bus connection block (C2) from the module .
Note
Don’t try to remove the bus connection block from the
bottom side. There is a risk of shorting-out the device!
Slipping on bus connection blocks
- Slip the bus connection block (C2) onto the guide slot
of the module and
- press the bus connection block (C2) down to the stop.
C2
C2.2
C2.1
C2.3
figure 9: Slipping off/on bus connection blocks
Connecting bus cables
- The bus connection block (D1) can be used with single
core conductors Ø 0.6…0.8 mm.
- Remove approx. 5 mm of insulation from the conduc-
tor (D2) and plug it into the bus connection block (D1)
(red = +, grey = -)