Technical Product-Information

August 2017

Control Module Box AP 118

5WG1 118-4AB01

Siemens AG

AP 118, page 5 / 6

Technical Manual

Infrastructure and Cities Sector, Building Technologies
Control Products and Systems

© Siemens AG 2017

Update: http://www.siemens.com/gamma

P. O. Box 10 09 53, D-93009 Regensburg

Subject to change without further notice.

2.4.2.11/5

figure 6: dismounting an RS module

Mounting of an RL module:

- AP 118: Remove the lid of the Control Module Box.
- Insert the RL module (B2) into the hinge (B13) of the

mounting location (B4). The terminals (B14) point away
from the insertion point for the bus terminal (B11). The
type label (B3) is on top.

- Swivel the RL module (B2) down until it audibly snaps

into the mounting location (B4).

- Insert the bus terminal (B12) of the mounting location

(B4) onto the bus connection pins (B10) of the RL mod-
ule (B2).

- For assignment of the Physical Address press the learn-

ing button (B8) for a maximum of 2 seconds. The ad-
dressing mode is indicated when the LED is on (B9). It
returns to normal operating mode (LED Off) automati-
cally after receiving the physical address.

- Mount the lid again.

figure 7: mounting of an RL module

Dismounting an RL module:

- AP 118: Remove the lid of the Control Module Box.
- Remove the wiring from the terminals (B14).
- Remove the bus terminal (B12).
- To remove the RL module (B2), insert a screw driver

between the module and the mounting location on the
bus terminal side and push it up to release it from the
snap-in hooks.

- Swivel the RL module (B2) up, pull it down out of the

hinge (B13) and remove it from the mounting location
(B4).

- Mount the lid again.

figure 8: dismounting an RL module

Wiring
Slipping off/on bus connection blocks

The bus connection block (C2) is situated on the back of
the actuator (C1).
It consists of two components (C2.1 and C2.2) with four
terminal contacts each. Take care not to damage the two
test sockets (C2.3) by accidentally connecting them to
the bus cable or with the screw driver (e.g. when at-
tempting to unplug the bus connection block).

Slipping off bus connection blocks
-  Carefully put the screw driver to the wire insertion slit

of the bus connection block’s grey component (C2.2)
and

-  pull the bus connection block (C2) from the module .

Note

Don’t try to remove the bus connection block from the
bottom side. There is a risk of shorting-out the device!

Slipping on bus connection blocks
-  Slip the bus connection block (C2) onto the guide slot

of the module and

-  press the bus connection block (C2) down to the stop.

C2

C2.2  

C2.1

C2.3

figure 9: Slipping off/on bus connection blocks

Connecting bus cables
-  The bus connection block (D1) can be used with single

core conductors Ø 0.6…0.8 mm.

-  Remove approx. 5 mm of insulation from the conduc-

tor (D2) and plug it into the bus connection block (D1)
(red = +, grey = -)

Содержание AP 118

Страница 1: ...tuator 2 x 6A 5WG1 525 2AB23 Universal dimmer 1 x 250VA The mounted module is connected to the bus line via a bus terminal block The AP 118 Control Module Box provides wiring space with room for two connectors for PE and N conductors This allows for secure connection of the PE and N con ductors of the cables inserted into the AP 118 Control Module Box For strain relief cables can be secured at the...

Страница 2: ... category according to IEC 60664 1 III Bus safety extra low voltage SELV DC 24 V Environmental specifications Climatic withstand capability EN 50090 2 2 Ambient temperature operating 5 45 C Ambient temperature non op 25 70 C relative humidity non condensing 5 bis 93 CE norm complies with low voltage regulations Mounting and Connecting General description The Control Module Box is designed for on s...

Страница 3: ...separately A14 Clamp for strain relief cut off from base A2 A14 A7 A6 A11 A9 A4 A2 A14 A8 figure 2b Mounting Removing the lid of the Control Module Box Remove the screws A3 securing the lid Pull the latching clamp A4 away from the lid A5 lift the lid up swivel it up and remove it from the hinge A6 Mounting the lid of the Control Module Box Hook the lid A5 into the hinge A6 Push the lid A5 down unt...

Страница 4: ... with 0 6 0 8 mm Ø B13 Hinge joint for mounting hinge of the RL module B14 Terminals Mounting of a RS module AP 118 Remove the lid of the Control Module Box Insert the bus connection module B5 in such a way into the insertion point B6 for the bus connection module that the bus connection pins B10 point to the insertion point for the bus terminal B11 Press the bus connection module B5 down until it...

Страница 5: ...he bus terminal B12 To remove the RL module B2 insert a screw driver between the module and the mounting location on the bus terminal side and push it up to release it from the snap in hooks Swivel the RL module B2 up pull it down out of the hinge B13 and remove it from the mounting location B4 Mount the lid again figure 8 dismounting an RL module Wiring Slipping off on bus connection blocks The b...

Страница 6: ...uits are connected via screwless plug in terminals E1 Remove approx 9 10 mm of insulation from the wire E 1 1 and plug it into the terminal E1 The terminals are designed for connection of two wires allowing to loop through the terminal block Note The maximum permissible terminal load current is 16A Remove wires Press the terminal interlocking of the terminal F1 with a screw driver and remove the w...

Отзывы: