WL Circuit Breaker
Communication-capable Circuit Breakers
2/5
Functional overview of the trip unit system
Basic Functions
ETU748
ETU755
ETU776
Long-time overcurrent protection
✔
✔
✔
Function can be switched ON/OFF
–
–
–
Setting range
IR = In x …
0.4, 0.45, 0.5, 0.55,
0.4 … 1 (step: 1A)
0.4 … 1 (step: 1A)
0.6, 0.65, 0.7, 0.8,
0.9, 1
Switch-selectable overload protection
(
I2t or I4t dependent function)
✔
✔
(via communications)
✔
Setting range of time delay class
tR at I
2t
(seconds)
2, 3.5, 5.5, 8, 10,
2 … 30 (step: 0.1s)
2 … 30 (step: 0.1s)
14, 17, 21, 25, 30
Setting range of time delay
tR at I
4t
(seconds)
1, 2, 3, 4, 5
1 … 5 (step: 0.1s)
1 … 5 (step: 0.1s)
Thermal memory
✔
(via slide switch)
✔
(on/off via communications)
✔
(on/off via key pad
or communications)
Phase loss sensitivity
at
tsd=20ms (M)
✔
(on/off via communications)
✔
(on/off via key pad
or communications)
Neutral protection
–
✔
✔
Function can be switched ON/OFF
✔
(via slide switch)
✔
(via communications)
✔
(via keypad or communications)
N-conductor setting range
IN = In x …
0.5, 1, OFF
0.5, 1, OFF
0.5 … 2, OFF
Short-time delayed overcurrent protection
✔
✔
✔
Function can be switched ON/OFF
–
✔
(via communications)
✔
(via key pad or communications)
Setting range
Isd = In x …
1.25, 1.5, 2, 2.5,
1.25 … 0.8 x Icw = max
1.25 … 0.8 x Icw = max
3, 4, 6, 8, 10, 12
(step: 10A)
(step: 10A)
Setting range of time delay
tsd, fixed
(seconds)
M, 0.1, 0.2, 0.3, 0.4
M, 0.08 … 0.4, OFF (step: 0.001s)
M, 0.08 … 0.4, OFF (step: 0.001s)
Switch-selectable short -time delay
short-circuit protection
(
I2t dependent function)
✔
(via rotary switch)
✔
(via communications)
✔
(via key pad or communications)
Setting range of time delay
tsd at I
2t
(seconds)
0.1, 0.2, 0.3, 0.4
0.1 … 0.4 (step: 0.001s)
0.1 … 0.4 (step: 0.001s)
Zone Selective Interlocking (ZSI) function
per CubicleBUS module
per CubicleBUS module
per CubicleBUS module
Instantaneous overcurrent protection
✔
✔
✔
Function can be switched ON/OFF,
Extended Instantaneous Protection
is enabled when OFF
–
✔
(via communications)
✔
(via key pad or communications)
Setting range
Ii = In x …
–
I
i
=
I
cw
= EIP
1.5 x
I
n
… 0.8 x
I
cs
= max, OFF=
I
cw
=EIP
1.5 x
I
n
… 0.8 x
I
cs
= max, OFF=
I
cw
=EIP
Ground fault protection
O
(field installable module)
O
(field installable module)
O
(field installable module)
Trip and alarm function
✔
✔
(via communications)
✔
(via key pad or communications)
Detection of the ground fault current
by residual summing method
✔
✔
✔
Detection of the ground fault current
by direct sensing method
✔
✔
✔
Setting range of the
Ig for trip
A, B, C, D, E
A … E (step: 1A)
A … E (step: 1A)
Setting range of the
Ig for alarm
A, B, C, D, E
A … E (step: 1A)-
A … E (step: 1A)
Setting range of the time delay
tg
(seconds)
0.1, 0.2, 0.3, 0.4, 0.5
0.1 … 0.5 (step: 0.001s)
0.1 … 0.5 (step: 0.001s)
Switch-selectable
ground fault protection
(
I2t / fixed)
✔
✔
✔
Setting range time delay
tg at I
2t
0.1, 0.2, 0.3, 0.4, 0.5
0.1 … 0.5 (step: 0.001s)
0.1 … 0.5 (step: 0.001s)
ZSI ground function
per CubicleBUS module
per CubicleBUS module
per CubicleBUS module
✔
available
–
not available
O
optional
L
N
S
I
G
Extended Instantaneous Protection (EIP) allows the WL breaker to be applied at the withstand rating of
the breaker with minus 0% tolerance; that means no instantaneous override whatsoever. EIP further
enables the circuit breaker to be applied up to the full instantaneous rating of the breaker on systems
where the available fault current exceeds the withstand rating.
Ground Fault Module cannot be removed after installation.
1
2
Notes:
M
= Indicates phase loss sensitivity is enabled. LT pickup reduced 80% when phase unbalance > 50%. ST delay = 20 ms
Communications
= Setting the parameters of the trip unit via the Breaker Data Adapter or PROFIBUS
Key pad
= Direct input at the trip unit
In
2
1
1
WL PROFIBUS Communication and Electronic Accessories • July 2004