2000590-001
Data Communications Setup
••
45
Command Summary
This section summarizes the command syntax for the Advance Network
Gateway (ANG_EN) software.
Adds an ADH Unit to the Address Translation Table
format:
add adh loop unit
Where
loop
is a number in the range 1- 8.
Where
unit
is a number in the range 1-31.
This command permits configuration of the ANG_EN
format:
config display
format:
config time server ip xxx.xxx.xxx.xxx
Where
xxx.xxx.xxx.xxx
is the IP address of the time server
format:
config address ip xxx.xxx.xxx.xxx
Where
xxx.xxx.xxx.xxx
is the IP address.
format:
config address ethernet xx.xx.xx.xx.xx.xx
Where
xx.xx.xx.xx.xx.xx
is the Ethernet address.
format:
config loop x
Where
x
is a number in the range 1-8.
format:
config unit x
Where
x
is a number in the range 1-31.
format:
config iproute xxx.xxx.xxx.xxx
Where
xxx.xxx.xxx.xxx
is the IP address.
format:
config netmask xxx.xxx.xxx.xxx
Where
xxx.xxx.xxx.xxx
is the IP address.
Deletes the specified ADH Unit from the Address Translation Table
format:
del all
format:
del adh loop unit
Where
loop
is a number in the range 1- 8.
Where
unit
is a number in the range 1-31.
format:
del ip xxx.xxx.xxx.xxx
Where
xxx.xxx.xxx.xxx
is the IP address.
Generates display of the specified ADH Unit(s) from the ATT
format:
display all
format:
display adh loop unit
Where
loop
is a number in the range 1-8.
Where
unit
is a number in the range 1-31.
loop
&
unit
are optional parameters
no options defaults to this ANG_EN loop
loop
only displays all Units in specified loop
loop unit
displays specified ADH unit
format:
display ip xxx.xxx.xxx.xxx
Where
xxx.xxx.xxx.xxx
is the optional IP address.
no option defaults to this ANG_EN IP
Description
add
config
del
display