background image

CA1Q4895en
2016-03-24

Building Technologies

OEM

Electrical Actuators

for valves VVP459.., VXP459.., VMP459..,
VXG48.., VXI48.., VVG549..

 SSC319
 SSC819
 SSC619

SSC319

operating voltage AC 230 V

3-position control signal

SSC819

operating voltage AC 24 V

3-position control signal

SSC619

operating voltage AC/DC 24 V

DC 0…10 V control signal

Nominal force 300 N
Automatic identification of valve stroke
Direct mounting with coupling nut, no tools required
Cable connection via screw terminals
Manual override with indication of position and direction of travel
Parallel connection of multiple actuators

Use

For operation of Siemens 2-port and 3-port valves with a nominal stroke of 5.5 mm for
water-side control of hot water and cooling water in heating, ventilation and air
conditioning systems

Содержание acvatix SSC319

Страница 1: ...AC DC 24 V DC 0 10 V control signal Nominal force 300 N Automatic identification of valve stroke Direct mounting with coupling nut no tools required Cable connection via screw terminals Manual override with indication of position and direction of travel Parallel connection of multiple actuators Use For operation of Siemens 2 port and 3 port valves with a nominal stroke of 5 5 mm for water side con...

Страница 2: ...ds valve opens Voltage at Y2 Actuator stem retracts valve closes No voltage at Y1 or Y2 Actuator maintains the current position The valve opens closes in proportion to the control signal at Y At DC 0 V the valve is fully closed A AB When power supply is removed the actuator maintains its current position When the AC DC 24 V supply is applied for the first time the actuators calibrate themselves in...

Страница 3: ...rs should be installed so that they are initially in position 0 also refer to Manual override 90 4362Z01 90 When commissioning the system check wiring and the functions of the actuator Before testing the functioning of the SSC always check to ensure that the actuator concerned is mounted on a valve refer to Equipment combinations Calibrating the SSC619 without a valve connected causes the actuator...

Страница 4: ...place The SSC actuators cannot be repaired They must be replaced as a complete unit Disposal The device is considered an electronics device for disposal in terms of European Directive 2012 19 EU and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable laws and regulations Warranty The technical re...

Страница 5: ...r residential commercial and light industrial environments Product standard EN60730 x EU Conformity CE A5W90000898 A5W90000900 A5W90000899 RCM Conformity A5W90000923_A A5W90000925_A A5W90000924_A EAC Conformity Eurasia Conformity Protection class to EN 60730 II III Contamination level EN 60730 Class 2 Housing protection Upright to horizontal IP40 to EN 60529 UL approbation UL 873 cUL approbation C...

Страница 6: ...24 V Connection diagrams 4864A01 L N L N AC 230 V N Y2 Y1 2AF N Y1 Y2 Q1 Q2 Y N Controller Y Actuator L System potential AC 230 V N System neutral Y1 Y2 Control signal OPEN CLOSE Q1 Q2 Controller contacts 4864A02 Y1 G G0 SP SN AC 24 V G Y2 Y1 Y2 N Q1 Q2 2AF Y N Controller Y Actuator SP G System potential AC 24 V SN G0 System neutral Y1 Y2 Control signal OPEN CLOSE Q1 Q2 Controller contacts 4864A03...

Страница 7: ...ors CA1Q4895en Building Technologies 2016 03 24 Dimensions All dimensions in mm 48 110 8 89 2 21 6 115 1 132 5 4895Z08 G Revision numbers Type reference Valid from Rev No Type reference Valid from Rev No SSC319 J SSC619 J SSC819 J ...

Страница 8: ...d by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2007 Technical specifications and availability subject to change without notice ...