4 / 14
Siemens
A6V10881143_en--_e
Smart Infrastructure
2021-06-17
HMI (Human-Machine Interface)
For more detailed explanations on device states, functions and error display, cf. product
documentation CE1Z4634
1)
.
Push-button operation
Activity
Push-button operation
Confirmation
Display current address
(in reverse order)
Press button < 1s
Current address is displayed
Enter Modbus address with push-button Press button > 1s and < 5s
See description next page
Enter push-button addressing mode
(for use with Climatix
TM
controllers)
Press button > 5s and < 10s
LED shines orange (release
button when red LED gets
dark). Timeout after 1 min.
Reset to factory settings
Press button > 10s
LED flashes orange
LED colors and patterns
Color
Pattern
Description
Green
steady
Start-up
1s on / 5s off
Fault free operation (“life pulse”)
flashing
Bus traffic
Orange / green
1s orange / 1s green Device is in override control
Orange
1s on / 1 off
Bus parameters not yet configured
Orange
1s on / 5s off
Backup mode entered
Red
Steady
Mechanical fault / device jammed
1s on / 5s off
Internal error
0.1s on / 1s off
Invalid configuration, e.g. Min = Max
Resetting the device by push button
The rotary actuators can be reset by push-button:
1. Press button for >10s
LED starts flashing
orange
2. Release button while LED still flashes
LED keeps flashing for 3s
3. If the button is pressed within these 3s, the reset is cancelled.
4. After those 3s
LED shines
red
(reset), then
green
(start-up).
1)
Related documents such as environmental declarations, CE declarations, etc., can be
downloaded at the following Internet address:
http://siemens.com/bt/download