background image

 

 

 

13 / 14 

A6V10881143_en--_e 

 

Siemens 

2021-06-17 

 

Smart Infrastructure 

Diagrams 

Internal diagrams 

The rotary actuators are supplied with a prewired connecting and communication cable. All 
interconnected devices must be connected to the same G0. 

Core 
desig. 

Core color  Terminal 

code 

Description 

  

red (RD) 

System voltage AC 24 V 

black (BK) 

G0 

System neutral AC 24 V 

violet (VT) 

REF 

Reference 

grey (GY) 

Bus (Modbus RTU) 

pink (PK) 

Bus (Modbus RTU) 

 
 

Note 

The operating voltage at terminals G and G0 must comply with the requirements under 
SELV or PELV. Safety transformers with twofold insulation as per EN 61558 required; they 
must be designed to be on 100 % of the time. 

 

 

Dimensions 

Actuator 

 

Dimensions in mm 

 

=  > 100 mm 

  =  > 200 mm

 

 

Minimum clearance from ceiling or wall for mounting,  

connection, operation, maintenance etc. 

b

6

5

7

M

0

1

b

 

Содержание Acvatix G B111.9E/MO Series

Страница 1: ...nal torque GLB111 9E MO with 10 Nm nominal torque Operating voltage AC 24 V For air handling units AHU and other heating cooling applications Modbus RTU communication UL listed For 2 port and 3 port control ball valves internally threaded connections VAI61 and VBI61 or externally threaded connections VAG61 and VBG61 DN15 to DN50 For 6 port control ball valve externally threaded connections VWG41 D...

Страница 2: ...ers 06 Write Single Register 16 Write Multiple registers max 120 registers within one message For a detailed description of specific functions please refer to the product documentation CE1Z4634 Type summary Product no Stock no Operating voltage Positioning signal Power consumption Posit time Manual adjuster Position feedback GLB111 9E MO S55499 D206 AC 24 V Modbus RTU 1 VA 0 5 W 3 VA 2 5 W 1 150 s...

Страница 3: ...I61 32 16 Rp 1 VBG61 32 16 G 2 B 16 32 VBI61 40 25 Rp 1 VBG61 40 25 G 2 B 25 40 VBG61 50 40 G 2 B 40 50 VBI61 50 Rp 2 40 63 50 1 Data sheet N4211 2 Data sheet N4212 VWG41 6 port control ball valve Ball valves with kvs m3 h DN G B1 9E internal threads Rp external threads5 G B pmax ps VWG41 20 G1B 0 25 4 25 20 200 5 Data sheet A6V10564480 Product no Stock no Description Doc type Doc number AST20 S55...

Страница 4: ...s and patterns Color Pattern Description Green steady Start up 1s on 5s off Fault free operation life pulse flashing Bus traffic Orange green 1s orange 1s green Device is in override control Orange 1s on 1 off Bus parameters not yet configured Orange 1s on 5s off Backup mode entered Red Steady Mechanical fault device jammed 1s on 5s off Internal error 0 1s on 1s off Invalid configuration e g Min M...

Страница 5: ... is repeated one times for confirmation Note If button is released before LED shines red the address is discarded Examples Set address 124 1 Enter addressing mode 2 Set 1 digits Press button 4 times LED flashes red per button press 3 Store 1 digits press button until LED shines green release button 4 Set 10 digits Press button 2 times LED flashes green per button press 5 Store 10 digits press butt...

Страница 6: ...rs 257 Opening direction RW 0 CW 1 CCW 258 Adaptive Mode RW 0 Off 1 On 259 Operating Mode RW 1 POS 260 MinPosition RW 0 01 0 100 261 MaxPosition RW 0 01 0 100 262 Actuator Running Time R s 1 150 513 Backup Mode RW 0 Go to BackupPosition 1 Keep last position 2 Disabled 514 Backup Position RW 0 01 0 100 515 Backup Timeout RW s 1 0 65535 516 Startup Setpoint RW 0 01 0 100 764 Modbus Address RW 1 247 ...

Страница 7: ... Char_16 1 R Each register Two bytes each coding an ASCII char ASN is coded beginning with reg 1409 Example 0x47 44 GD 0x42 31 B1 0x38 31 81 0x2E 31 1 0x45 2F E 0x4D 4F MO ASN GDB181 1E MO Register 769 Status Status Bit 00 1 Reserved Bit 06 1 Not available Bit 01 1 Backup mode active Bit 07 1 Not available Bit 02 1 Not available Bit 08 1 Not available Bit 03 1 Not available Bit 09 1 Self test fail...

Страница 8: ...g instr A6V10920701 1 1 Related documents such as environmental declarations CE declarations etc can be downloaded at the following internet address http siemens com bt download Engineering GDB 9E actuators may only be used at medium temperatures 0 C If condensation occurs at the mounting site the use of the temperature adapter ALJ100 is recommended in order to protect the actuator If the medium t...

Страница 9: ...n nection between the Modbus master programming tool and peripheral devices i e non conflicting addresses and matching baudrate transmission format Full configuration over bus If the address is unique per segment when powered up the device can be accessed by the Modbus master or programming tool and the address and other parameters can then be set to the definitive values Partial configuration ove...

Страница 10: ...device for disposal in terms of European Directive 2012 19 EU and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable laws and regulations Warranty Technical data on specific applications are valid only together with Siemens products listed under Equipment combinations Siemens rejects any and all...

Страница 11: ...rmissible medium temperature in the valve in combination with GDB actuators 0 120 C Connection cables Cable length 0 9 m Power supply Communication Number of cores and cross sectional area 5 x 0 75 mm2 Service interface Terminal strip 7 pin grid 2 00 mm Communication Communication protocol Modbus RTU RS 485 galvanically separated Number of nodes Max 32 Address range 1 248 255 Default 255 Transmiss...

Страница 12: ...ic compatibility Application For residential commercial and industrial environments GLB111 9E MO GDB111 9E MO EU Conformity CE A5W00000176 1 A5W0003842 1 RCM Conformity A5W00000177 1 A5W0003843 1 UL cUL AC 24 V UL 873 http ul com database Environmental compatibility The product environmental declaration A6V10209938 1 contains data on environmentally compatible product design and assessments RoHS c...

Страница 13: ... voltage AC 24 V 2 black BK G0 System neutral AC 24 V 6 violet VT REF Reference 8 grey GY Bus Modbus RTU 9 pink PK Bus Modbus RTU Note The operating voltage at terminals G and G0 must comply with the requirements under SELV or PELV Safety transformers with twofold insulation as per EN 61558 required they must be designed to be on 100 of the time Dimensions Actuator Dimensions in mm 100 mm 200 mm M...

Страница 14: ... 58 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2021 Technical specifications and availability subject to change without notice Dokument ID A6V10881143_en _e Ausgabe 2021 06 17 Temperature adapter optional Revision numbers Type Valid from rev no GLB111 9E MO B GDB111 9E MO C 42 70 64 162 8 23 5 ...

Отзывы: