5 / 12
A6V10725318_en--_e
Siemens
2018-06-05
Building Technologies
HMI (Human-Machine Interface)
Push-button operation
Activity
Push-button operation
Confirmation
Enter / leave addressing mode
Press button <1 s
LED turns red or gets off
Reset to factory settings
Press button >20 s
LED flashes orange until device
restarts
PL-Link connection test
1)
Press key >2 s and <20 s
LED flashes 1x orange
1)
Function or part of the function available in PL-Link operation only
LED colors and patterns
Color
Pattern
Description
Off
---
Fault free operation or device not powered
Green
steady
Connection test successful
1)
Orange
flashing
a) Factory reset in progress
b) When a connection test was triggered: wait
1)
Red
steady
a) Device is in programming/addressing mode
b) When a connection test was triggered: Connection test failed
1)
1)
Function or part of the function available in PL-Link operation only
Addressing and bus test with push button
The rotary actuators can be set into addressing/programming mode by push-button:
∂
Press push button (<1 s)
∂
KNX bus wiring OK
⇓
LED turns red until addressing/programming is finished
∂
KNX bus wiring not OK
⇓
LED stays dark
Reset with push button
The rotary actuators can be reset by push-button:
∂
Press push button >20 s
∂
LED flashes orange
∂
Device restarts
All parameters are reset to the default values.