![Siemens 7XV5662-0AA00 Скачать руководство пользователя страница 52](http://html.mh-extra.com/html/siemens/7xv5662-0aa00/7xv5662-0aa00_directions-for-use-manual_381525052.webp)
English
7XV5662-0AA00
52
C53000-B1174-C134-7
Vibration and Shock Stress During Transport
Standards:
IEC 60255-21 and IEC 60068-2
– Vibration
Sinusoidal
IEC 60255-21-1, Class 2
5 Hz to 8 Hz:
±
7.5 mm Amplitude
IEC 60068-2-6
8 Hz to 150 Hz: 2 g acceleration
Frequency sweep rate 1 Octave/min
20 cycles in 3 orthogonal axes.
– Shock
Half-sine shaped
IEC 60255-21-2, Class1
Acceleration 15 g, duration 11 ms,
IEC 60068-2-27
3 shocks in each direction of
3 orthogonal axes.
– Continuous Shock
Half-sine shaped
IEC 60255-21-2, Class 1
Acceleration 10 g, duration 16 ms,
IEC 60068-2-29
1000 shocks in each direction of
3 orthogonal axes.
Climatic Stress Tests
Temperatures
IEC
60068–2
– Recommended temperature during operation
-5 °C to +55 °C or +23 °F to +131 °F
– Permissible temporary (transient)
operating temperature
-20 °C to +70 °C or -4 °F to +158 °F
– Type test (acc. IEC 60068–2–1 and –2
-25 °C to +85 °C or -13 °F to +185 °F
Test Bd for 16 h)
– Limit temperatures during storage
-40 °C to +85 °C or -40 °F to +185 °F
– Limit temperatures for operation
-40 °C to +85 °C or -40 °F to +185 °F
Storage and transport of the device with factory packaging!
Humidity
Admissible humidity conditions
yearly average
≤
75 % relative humidity;
on 56 days per year up to 93 % relative
humidity;
during operation, condensation not
permissible!
All devices shall be installed so that they are not exposed to direct sunlight, nor subject to
great fluctuations in temperature that may cause condensation to occur.
Содержание 7XV5662-0AA00
Страница 2: ...Deutsch 7XV5662 0AA00 2 C53000 B1174 C134 7 ...
Страница 56: ...English 7XV5662 0AA00 56 C53000 B1174 C134 7 ...
Страница 57: ...7XV5662 0AA00 C53000 B1174 C134 7 57 ...