7XV5662-0AA00
English
C53000-B1174-C134-7
45
LED3, RxD
The yellow LED “RxD” signals the received data (optical fibre –R), that comes from the
protection device and is to be transmitted to the mains interface.
LED4, Power On
The green LED “Power On” signals the activated auxiliary voltage.
Push button
The push button initiates a reset.
Also LEDs 1-3 are activated for the period during which the pushbutton is actuated, and
the DR relay is deactivated if it was activated. This makes possible a functional check of
these signalling elements.
The LED states during putting into operation are shown in the following six steps (for the
structure, see Figure 12).
Here, “ * ” means any undefined LED state (MAKE / BREAK / FLASHING).
Preconditions for putting into operation:
The jumper positions must correspond to the required operating mode / baud rate in both
KU–XGs (KU–XG1, KU–XG2).
Step 1 KU–XG1 is in the Power On state and the opposite terminal KU–XG2 is in the Power Off state
KU–XG1
KU–XG2
LED1
MAKE
LED1
BREAK
LED2
*
LED2
BREAK
LED3
*
LED3
BREAK
LED4
MAKE
LED4
BREAK
Step 2 Apply the interface (X.21 / G.703) on KU–XG1
KU–XG1
KU–XG2
LED1
BREAK
LED1
BREAK
LED2
*
LED2
BREAK
LED3
*
LED3
BREAK
LED4
MAKE
LED4
BREAK