7XG3124 Commissioning Guide
©2014 Siemens Protection Devices Limited
Chapter 3 Page 8 of 8
LED State
Meaning
On Solid
Healthy
Fast Flashing
(approx three times every sec)
CID loading error (61850 stack problem)
The .cid file is in error or possibly corrupted, open a web
server session where further information is reported on the
Relay Build page
Slow Flashing
(approx once every sec)
SNTP sync fail
Check SNTP server is functioning or check that the SNTP
Server address on the IP config screen is correct
Off
Internal RA24 Communications failure
A permanent Internal RA24 Communications failure will
assert the Service Alarm
Section 4: RA24 Power Supply Indications
4.1 Interpreting Vx Auxiliary Supply or Relay Healthy Indications
The Healthy LED will be illuminated solid to indicate normal operation of the RA24.
The Healthy LED is also utilised to indicate error conditions to assist in troubleshooting. The following
table summarises all Healthy LED indication
Table 10: Relay Healthy Indications