Chapter 2) 7XG3124 Application Guide
©2014 Siemens Protection Devices Limited Chapter 2 Page 37 of 42
4.4 Binary Output Allocation for Circuit Breaker Tripping
The following User Output to Binary Output allocations complete our ARC Fault Trip with Current Check.
SARC Operation
Zone Coverage
User Output Binary Output Trip
SARC 1
Feeder Exit Termination
Chamber
User Output 1 BO2
1A CB
SARC 2
Feeder CB Chamber
User Output 2 BO3
TR1 LT CB
SARC 3 or SARC 4
Bus
User Output 2 BO3
TR1 LT CB
SARC 5
Incomer CB Chamber
User Output 3 BO4
Upstream
SARC 6
Incomer Termination
Chamber
User Output 3 BO4
Upstream
Table 6: Binary Output Allocation
The screenshot shows the User Output to Binary Output allocation in the setting editor of Reydisp Manager.
Figure 46: Reydisp Relay Settings
Complete any other Protection settings otherwise required and save your setting.
4.5 Device Sync
With all IED settings, IED Logic and IEC61850 configuration complete we now need to
Synchronize the device.
Reydisp Manager will manage the file transfer process to the 7SR22 IED and upon completion the
7SR22 will be able subscribe to SARC Goose messages from the RA24 IED.
Содержание 7XG3124 ReyArc24
Страница 1: ...Energy Management 7XG3124 ReyArc24 Arc Fault Monitor Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7XG3124 Contents Page 2 of 2 2014 Siemens Protection Devices Limited ...
Страница 24: ...Chapter 1 7XG3124 Installation Guide 2014 Siemens Protection Devices Limited Chapter 1 Page 20 of 20 ...
Страница 66: ...Chapter 2 7XG3124 Application Guide 2014 Siemens Protection Devices Limited Chapter 2 Page 42 of 42 ...
Страница 75: ......