$SSHQGL[
80
9
&*&
1304 T-RESET
Reset delay after trip (definite stage)
min. 0.00
s
max. 32.00
©©©©
1305 WARN THERM
Thermal warning stage in % of trip temperature
min. 70
%
max. 99
©©©©
1306 T-WARN
Delay time of the warning stage
min. 0.00
s
max. 32.00
©©©©
1307 TIME MULT.
Time multiplier for U/f time characteristic
min. 1
max. 8
©©©©
1308 U/f
(1)
1st characteristic value of overflux U/f
min. 1.02
max. 1.60
©©©©
1309 T-U/f (1)
Time delay T of 1st characteristic value
min. 1
s
max. 98/Ñ
©©©©
1310 U/f
(2)
2nd characteristic value of overflux U/f
min. 1.02
max. 1.60
©©©©
1311 T-U/f (2)
Time delay T of 1st characteristic value
min. 1
s
max. 98
©©©©
1312 U/f
(3)
3rd characteristic value of overflux U/f
min. 1.02
max. 1.60
©©©©
1313 T-U/f (3)
Time delay T of 1st characteristic value
min. 1
s
max. 98
©©©©
1314 U/f
(4)
4th characteristic value of overflux U/f
min. 1.02
max. 1.60
©©©©
1315 T-U/f (4)
Time delay T of 1st characteristic value
min. 1
s
max. 98
©©©©
1316 U/f
(5)
5th characteristic value of overflux U/f
min. 1.02
max. 1.60
©©©©
1317 T-U/f (5)
Time delay T of 1st characteristic value
min. 1
s
max. 98
©©©©
1318 U/f
(6)
6th characteristic value of overflux U/f
min. 1.02
max. 1.60
©©©©
www
. ElectricalPartManuals