$SSHQGL[
80
9
&*&
¿©©©©§©©©©©©©©©©©©©§©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©§©©§©©§©§©©©¤
FNo.Abbreviation Meaning
OpFtEIOT
¨©©©©ª©©©©©©©©©©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©ª©©©
5369RM th. repl. Reset memory of thermal replica U/f
CG O
5370U/f> Fault
Overexc. prot.: Fault detec. U/f>
CG O
5371U/f> Trip
Overexc. prot.: Trip of U/f> stage
C OT
5372U/f> th.Trip Overexc. prot.: Trip of th. stage
C OT
5383>R/E/F block >Block rotor earth fault protection
IO
5386>Test R/E/F >Activate test operation via BI
CG IO
5391R/E/F off
Rotor earth fault prot. is switched offCG O
5392R/E/F blockedRotor earth fault prot. is blocked
CG O
5393R/E/F active Rotor earth fault prot. is active
CG O
5395R/E/F open
Open circuit meas. circuit R/E/F
CG O
5396Failure R/E/FFailure rotor earth fault protection
CG O
5397R/E/F Warn
Rotor earth fault prot.: Warning stage CG O
5398R/E/F Fault Rotor earth fault prot.: Fault detec. CG O
5399R/E/F Trip
Rotor earth fault prot.: Trip
C OT
5402Failure RMT Failure rotating meas. value transm.
CG O
5404Test REF warnR/E/F warning stage during test
CG O
5405Test REF TripR/E/F Trip during test operation
C O
5413>I/T block
>Block interturn fault protection
IO
5421I/T off
Interturn fault prot. is swiched off
CG O
5422I/T blocked Interturn fault prot. is blocked
CG O
5423I/T active
Interturn fault prot. is active
CG O
5426I/T Fault
Interturn fault prot.: Fault detec.
CG O
5427I/T Trip
Interturn fault prot.: Trip
C OT
5473>SEF block
>Block Stator earth fault protection
IO
5476>U20 failure >Failure 20Hz bias voltage (S/E/F)
CG IO
5481S/E/F off
S/E/F protection is switched off
CG O
5482S/E/F blockedStator earth fault prot. is blocked
CG O
5483S/E/F active Stator earth fault prot. is active
CG O
5486Failure S/E/FFailure stator earth fault protection CG O
5487S/E/F warn
Stator earth fault prot. warning stage CG O
5488S/E/F Fault Stator earth fault prot.: Fault detec. CG O
5489S/E/F Trip
Stator earth fault prot.: Trip
C OT
6506>U< block
>Block undervoltage protection U< stage IO
6513>o/v block
>Block overvoltage protection
IO
6530U< off
Undervoltage protection is switched offCG O
6531U< blocked
Undervoltage protection is blocked
CG O
6532U< active
Undervoltage protection is active
CG O
6533U< Fault
Undervoltage fault detection U<
CG O
6539U< Trip
Undervoltage protection, U< trip
C OT
6565o/v off
Overvoltage protection is switched off CG O
6566o/v blk
Overvoltage protection is blocked
CG O
6567o/v active
Overvoltage protection is active
CG O
6568U> Fault
Overvoltage fault detection U>
CG O
6570U> Trip
Overvoltage protection U> trip
C OT
6571U>> Fault
Overvoltage prot. fault detec. U>>
CG O
6573U>> Trip
Overvoltage protection U>> trip
C OT
6872>Trip rel 1 >Trip circuit superv. trip relay 1
IO
6873>CBaux 1
>Trip circuit superv. CBaux 1
IO
6879Failure Trip1Failure trip circuit 1
CG O
6892>Trip rel 2 >Trip circuit superv. trip relay 2
IO
6893>CBaux 2
>Trip circuit superv. CBaux 2
IO
6899Failure Trip2Failure trip circuit 2
CG O