User Guide

Modes of Operation:
i)  Under-speed Mode:  The relay checks whether the speed of the

monitored system is lower than a particular set-point, defined as Set-
point

 Low. R2 is energized when the 

frequency of rotation

 becomes

lower than Set-Point Low.

ii) Over-Speed Mode:  The relay checks whether the speed of the

monitored system is greater than a particular set-point, defined as Set-

Point High. R1 is energized when the frequency of rotation becomes
greater than Set-Point High

iii) Dual-speed Mode:  The relay checks whether the speed of the

monitored system is within a particular range,  defined as Set-Point

Low to Set-Point High. R2 is energized when the frequency of rotation
becomes lower than Set-point Low. R1 is energized when the frequency
of rotation becomes greater than Set-point High.

Note: Relay 1 has been assigned for Over-speed and Relay 2 has been
assigned for Under-speed by default. These cannot be interchanged.

Both the relays are NOT energized when the connected motor is operating
within the preset range.

Scale Factor:
The user programmable scale factor facilitates the direct reading in
desired engineering unit. The counter multiplies the number of pulses
received at the count input with the scale factor, and displays the result.

Rate display = Number of pulses received per minute x scale factor or No.
of pulses received per hour x scale factor.

The scale factor consists of two parts, mantissa and exponent. The
mantissa can be set from 0.001 to 9.999 and the exponent can be set
from -3 to +2.

The scale factor is arrived at as:
Scale factor = Mantissa X 10

Exponent

Scale Factor cannot be 0 for obvious reasons.

Initial Time Delay (ITD):  It is the time required by the motor to gain opti-
mum speed. When the ITD is entered and unit is powered ON, the unit
waits for the ITD to elapse (in addition to TTD) before switching the relay
outputs in case of any unhealthy condition.

Trip Time Delay (TTD): Sometimes the motor speed can go out of range
for a while. In order to avoid the relay tripping due to such momentary
changes in frequency, Trip time delay is provided. The relay trips only if
unhealthy speed ensues after TTD has elapsed.

Relay reset modes: This feature allows one to customize the operating of
both the relay outputs R1 and R2, according to one’s requirement.

Auto-reset: The relay outputs R1 and R2 become de-energized when the
speed of the connected equipment comes back to the prescribed range.

Manual-reset: Once the relay outputs R1 and/ R2 become energized, they
stay energized even after the connected motor or any supported equip-
ment comes back to healthy speed. In order to de-energize the relays, the
user will have to press the assigned key.

R1

R1

R1

ITD

TTD

ITD

TTD

TTD

TTD

R2

Over Speed

Mode

Under Speed

Mode

Dual Speed

Mode

Mode of operation

Healthy

condition

Over

Range

R2

R2

Under
Range

R1 OFF

R1 ON

R2 OFF

R1 ON

R2 ON

R2 ON

R2 OFF

R2 OFF

Dimensional drawings

Siemens Ltd.

Product development is a continuous process. Consequently 

the data indicated in this Leaflet is subject to change without 
prior notice. For latest issue contact our sales offices.

SACHIN ENTERPRISE

Disposal

Siemens product are environment friendly, which predominantly 
consist of recyclable materials.
For disposals we recommend disassembling and separation into 
following materials:
METALS: Segregate into Ferrous & Non Ferrous types for recycling 
through authorised dealer.

PLASTICS: Segregate as per material type for recycling through 
authorised dealer. Because of the long lifetime of Siemens 
products the disposal guidelines may be replaced by other national 
regulations when taking the product out of service.
The local customer care service is available at any time to answer 
disposal-related questions

Customer Care Toll free no. 1800 209 0987 

Email: [email protected]                                                        Order No.A5E43375408A/AB

Содержание 7UG0583-1CU20

Страница 1: ...tage Uc 110 240V AC DC Tolerance on Control supply 0 85x Uc 1 1x Uc Frequency 50 60Hz Operating temperature 0 to 50 C 95 RH non condensing Sensor Supply 12VDC 30mA 10 Short circuit protected Count inputs 5 to 30VDC from proximity switches encoders solid state devices or potential free contacts Trip Time delay 0 to 99 9 sec programmable Rate Range Auto ranging resolution User selectable RPS RPM RPH...

Страница 2: ...pe NPN COM to be shorted For three wire sensor connect the sensor to internal 12V as shown or use external supply 5 to 30V if required Note If the sensors require more than 30mA current use external power supply to power the sensors To reduce noise Use of Snubber across load is recommended Note 1 In Configuration mode Both the relays will turn OFF 2 Set Point High will only accept values greater t...

Страница 3: ...ess Relay Reset Mode To go to next page before 3 seconds is complete Key Blinking for 3 seconds Key Changes relay reset mode Range Default Auto Manual Auto To go to next page before 3 seconds is complete Key Blinking for 3 seconds To go to next page before 3 seconds is complete Key Key Changes mode of operating Dual Under Over Range Blinking for 3 seconds To go to next page before 3 seconds is com...

Страница 4: ...ddition to TTD before switching the relay outputs in case of any unhealthy condition Trip Time Delay TTD Sometimes the motor speed can go out of range for a while In order to avoid the relay tripping due to such momentary changes in frequency Trip time delay is provided The relay trips only if unhealthy speed ensues after TTD has elapsed Relay reset modes This feature allows one to customize the o...

Отзывы: