background image

1

s

Operating Instructions

Automatic Power Factor Controller Relay

7UG0571-1FT20

7UG0572-1GT20

7UG0

IEC 60947-5-1

Please read and understand these instructions before installing, 
operating, or maintaining the equipment.

DANGER

Hazardous voltage can cause death or serious injury.
Disconnect power before working on equipment.

CAUTION

Reliable functioning of the equipment is only ensured 
with certified components.
Overvoltage category III 
(Refer IEC 60947-1)

NOTICE

This product has been designed for environment A. Use of this product 
in environment B may cause unwanted electromagnetic disturbances in 
which case the user may require to take adequate mitigation measures.

Technical Data

Designation

7UG0571-1FT20

7UG0572-1GT20

Type

Automatic Power Factor Controller

Operating range

50 to 440 VAC (L-L)

30 to 250 VAC (L-N)

AC Network

3

Φ

 4W / 3

Φ

 3W / 2

Φ

 2W/ 1

Φ

 2W

Display parameters

Power Factor, True RMS voltage, Current,  Frequency, 

Power (KW, KVA, KVAr), Energy (KWh, KVAh), Temperature

Control Supply

90 to 250 VAC, 50/60Hz

Power consumption

15VA

Frequency range

50/60Hz

Operating temperature

0°C to 60°C

Humidity

upto 95% ,without moisture condensation

Alarm mode (relay output)

Over voltage, Under voltage, Over Compensate, Under Compensate,  

CT Polarity error, No Voltage, Step error, Over Temperature

Trip indication

Backlight turns to Orange

No. of relay outputs

(Additional 2 for Alarm and Fan)

12 

(Additional 2 for Alarm and Fan)

Rated current of relay outputs (@250VAC)

5A* (AC12), 1A (AC15)

CT Burden

20 mohms

Switching program

Automatic / Linear / Rotational

Mounting

Panel mounting

SCPD for relay output (For Short circuit current 
of 1kA as per IEC 60947-5-1)

6A, gL, HRC fuse

* 5A AC12 rating is for individual relay contact. If multiple relays are ON, relay AC12 rating will be limited to 1.2A @ 250V.

Содержание 7UG0571-1FT20

Страница 1: ...e 50 to 440 VAC L L 30 to 250 VAC L N AC Network 3Φ 4W 3Φ 3W 2Φ 2W 1Φ 2W Display parameters Power Factor True RMS voltage Current Frequency Power KW KVA KVAr Energy KWh KVAh Temperature Control Supply 90 to 250 VAC 50 60Hz Power consumption 15VA Frequency range 50 60Hz Operating temperature 0 C to 60 C Humidity upto 95 without moisture condensation Alarm mode relay output Over voltage Under voltag...

Страница 2: ...col Communication address Transmission Mode Data types Transmission distance Transmission speed Parity Stop bits RS AND 485 MODBUS RTU 1 to 255 Half duplex Float and Integer 500 Meter maximum 300 600 1200 2400 4800 9600 19200 in bps None Odd Even 1 or 2 7UG057 L N V I R C NO RS485 T1 T2 0 5 Nm 0 4 Nm 5 Solid 1 x 0 75 to 2 5 mm2 2 x 0 5 to 2 x 1 5 mm2 0 5 mm2 5 Stranded with end sleeve 1 x 0 5 to 2...

Страница 3: ...phase Displays current of 1st phase Displays THD of current of 1st phase Press key 1st time Displays active power of 1st phase Displays reactive power of 1st phase Displays apparent power of 1st phase Press key 3rd time Press key 2nd time Displays active energy of 1st phase Displays reactive energy of 1st phase Displays apparent energy of 1st phase Displays temperature OK OK OK Parameter Key Key P...

Страница 4: ...Trip Time No Yes Under Voltage Set No Yes Harmonics Range No Yes No Yes Over Voltage Set Step Error Step Error Setting CT Polarity Error Over Temperature Hysteresis Voltage Hysteresis PF Factory Default Yes No Temperature Range Setting Fan Setting Reset kVAh Reset Energy Password Correct Reset kWh No Yes Yes No Reset kVArh Bank 1 Bank 2 Bank 5 Bank 6 Bank 7 Bank 3 Bank 13 Bank 14 Bank 4 Bank 8 Ban...

Страница 5: ... customer wants to reset energy 5min 5min Inst 5min 5min NA Inst 5min 2 5min 1min Inst 1min 1min NA Inst 50 240V L N 85 415 L L ON OFF 50 277V L N 85 480 L L ON OFF ON OFF ON OFF ON OFF 20 to 80 ON OFF 0 100 ON OFF ON OFF 1 to 10 1 to 5 20 100 50 YES NO YES NO YES NO YES NO YES NO 0001 9999 ON OFF Name of Parameter No Voltage Release Trip time setting TRIP TIME Over Voltage Nomenclature Default Va...

Страница 6: ...02 CT Secondary A 1 100 100 1 9999 500 500000 1 255 1 5 Integer Integer 1 0x0000 0x0001 1 2 40010 1 0x0000 0x0001 0x0002 None Odd Even 40009 0x09 0x0A Parity Stop bit 0x0005 0x0006 9600 19200 Meaning Value Integer 1 0x0000 300 40008 0x08 Baud rate bps 0x0001 600 0x0002 1200 0x0003 2400 0x0004 4800 Formula to find address of individual Harmonic Note For Error 0 No Error 1 Error Present Meaning Cons...

Страница 7: ...irst out sequence This option will automatically switch in and out the capacitors according to the targeted power factor sensitivity setting and the re connection time setting This automatic switching program uses intelligent switching sequence The step switching sequence is not fixed and the program automatically selects the most appropriate steps to switch in or out in order to achieve shortest ...

Отзывы: