SITRANS P DS III (7MF4.33.. 7MF4.34.. 7MF4.35..)
A5E03434626-03, 06/2013
13
Installation configuration for gases
Install the transmitter above the pressure tapping point.
Lay the pressure tubing with a constant gradient to the pressure tapping point, so that any condensation produced can drain
in the main line and thereby avoid corruption of the measured values.
Installation configuration for vapor and liquid
Install the transmitter below the pressure tapping point.
Lay the pressure tubing with a constant gradient to the pressure tapping point so that any gas pockets can escape in the
main line.
3.3.2
Installation (except level)
Note
Damage to measuring cell
When installing the process connection of the pressure transmitter, do not rotate the housing. Rotating the housing may
damage the measuring cell.
To avoid damage to the device, tighten the threaded nuts of the measuring cell using a wrench.
Procedure
Attach the transmitter to the process connection with an appropriate tool.
See also
Introduction to commissioning (Page 24)
3.3.3
Fastening
Fastening without the mounting bracket
You can fasten the transmitter directly on the process connection.
Fastening with the mounting bracket
You can fasten the mounting bracket as follows:
●
On a wall or a mounting frame using two screws
●
On a vertical or horizontal mounting tube (Ø 50 to 60 mm) using a tube bracket
Fasten the transmitter mounting bracket using the two screws provided.