SMART 7KT0310 Manual
Measured variables
Measured variable
On display
On communication
Voltage V
L-N
, V
L-L
●
●
Current
●
●
Neutral current
●
●
Frequency
●
●
Power factor
●
●
Active power
●
●
Reactive power
●
●
Apparent power
●
●
Active energy (Import, Export, Total)
●
●
Reactive energy (Import, Export, Total)
●
●
Apparent energy
●
●
Max demand (current) over set demand period
●
●
Max demand (active, reactive and apparent power) over set demand
period
●
●
Phase angle of 3 phases
●
–
THD% (Current)
●
●
THD% (Voltage)
●
●
Individual harmonics (Current)
–
●
Individual harmonics (Voltage)
–
●
–
: Not there
●
: Available
Measuring accuracy
Measured variable
Error limits
Voltage V
L-N
0.5% of Full scale (300V AC)
Voltage V
L-L
Full scale 0.5%
Current
Phase Current: 0.5% of full scale
Neutral current: 1% of full scale
Frequency
0.1%
For L-N Voltage >20V,
For L-L Voltage >35V
Power factor
0.01 Digit
Active power
1%
Reactive power
1%
Apparent power
1%
Active energy
Class 1 (as per IEC 62053-21)
Reactive energy
Class 2 (as per IEC 62053-23)
Apparent energy
1%
Phase angle of 3 phases
1%
THD (Current)
1%
THD (Voltage)
1%
Harmonics (Current)
1%
Harmonics (Voltage)
1%
When measuring on external current transformers or voltage
transformers, the accuracy of the measurement depends on the
quality of the transformer.
IEC Standards
Description
Standard
Energy accuracy
IEC 62053-21 | Active energy
EMC requirements
IEC 61326-1: 2012
Degree of protection test (IP)
IEC 60529
Safety requirements
IEC 61010-1:2010 and
IEC 61010-2-030:2010
Vibration and mechanical shock
IEC 62052-11
Certifications
SMART 7KT multifunction meter conforms to IEC
standards, IPC electronics assembly standard and
RoHS