SMART 7KT0310 Manual
Communication
7
Protocol and interface
Protocol: Modbus RTU
Interface: Integrated RS485 interface
Communication parameters
Communication address
1 to 255
Transmission mode
Half duplex
Data types
Float and Integer
Transmission distance
500m maximum
Transmission Speed
300, 600, 1200, 2400, 4800,
9600, 19200 (in bps)
Parity
None, Odd, Even
Stop bits
1 or 2
Response Time
100ms Max & Independent, at
Baud rate
Connection diagram for communication
RS485-RS232
Converter
Master
Suggested
terminating resistor
(120 ohm, ¼ watt)
F2
F3
F4
F1
F2
F3
F4
F1
F2
F3
F4
F1
Contact sales for PC based monitoring software to
communicate with the meters.
Modbus register addresses list
Readable Parameters: [Length (Register): 2; Data Structure: Float]
Address
Hex Address
Parameter
30000
0x00
Voltage V1N
30002
0x02
Voltage V2N
30004
0x04
Voltage V3N
30006
0x06
Average Voltage LN
30008
0x08
Voltage V12
30010
0x0A
Voltage V23
30012
0x0C
Voltage V31
30014
0x0E
Average Voltage LL
30016
0x10
Current I1
30018
0x12
Current I2
30020
0x14
Current I3
30022
0x16
Average Current
30024
0x18
kW1
30026
0x1A
kW2
30028
0x1C
kW3
30030
0x1E
kVA1
30032
0x20
kVA2
30034
0x22
kVA3
30036
0x24
kVAr1
Address
Hex Address
Parameter
30038
0x26
kVAr2
30040
0x28
kVAr3
30042
0x2A
Total KW
30044
0x2C
Total KVA
30046
0x2E
Total KVAr
30048
0x30
PF1
30050
0x32
PF2
30052
0x34
PF3
30054
0x36
Average PF
30056
0x38
Frequency
30058
0x3A
Total net kWh
30060
0x3C
Total net kVAh
30062
0x3E
Total net kVArh
30064
0x40
kW Max Active Power
30066
0x42
kW Min Active Power
30068
0x44
kVAr Max Reactive Power
30070
0x46
kVAr Min Reactive Power
30072
0x48
kVA Max Apparent Power
30084
0x54
kWh1 (Imp)