E50417-K109U-C322-A
1
SIMEAS
31
1.15
Commissioning
Before switching the auxiliary voltage on, the conformance of
operating data and the values on the name plate must be checked.
The transducer is ready for operation after 15 minutes of warm-up
and will then meet the specified error limits.
Measuring output currents and voltages:
•
In order to measure the output currents, disconnect the line of
one of the terminals to be tested (17/18, 19/20, or 21/22) and
connect an amperemeter in series.
•
In order to measure the output voltages, connect a voltmeter
to the corresponding terminals (cf. above) or tap the voltage at
the terminal screws with the test probes of the instrument.
Note:
Outputs set to load-independent current change to 25 V DC
maximum when opening the output circuit. This can be avoided
by disconnecting the auxiliary supply during the connection
procedure.
1.16
Servicing
The transducer does not require servicing. If necessary, it can be
checked in a laboratory and be recalibrated. The PC program
"SIMEAS PAR", run under WINDOWS
versions 3.1, 3.11, and
95, is used for calibration.
Содержание 7KG6000-8AA
Страница 37: ...E50417 K109U C322 A1 SIMEAS 37 ...
Страница 38: ...38 SIMEAS E50417 K109U C322 A1 ...
Страница 39: ...E50417 K109U C322 A1 SIMEAS 39 ...
Страница 67: ...E50417 K109U C322 A1 SIMEAS 67 ...
Страница 68: ...68 SIMEAS E50417 K109U C322 A1 ...
Страница 69: ...E50417 K109U C322 A1 SIMEAS 69 ...
Страница 76: ...76 SIMEAS E50417 K109U C322 A1 ...
Страница 78: ...78 SIMEAS E50417 K109U C322 A1 Pv Вт ...
Страница 79: ...E50417 K109U C322 A1 SIMEAS 79 Примечания ...
Страница 80: ...80 SIMEAS E50417 K109U C322 A1 ...
Страница 81: ...E50417 K109U C322 A1 SIMEAS 81 ...
Страница 82: ...82 SIMEAS E50417 K109U C322 A1 ...