Product overview
2.1 Properties
IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0)
Equipment Manual, 10/2020, A5E03576904-AE
11
You can find more information in the Server module
http://support.automation.siemens.com/WW/view/en/63257531
) manual.
First BaseUnit of an ET 200SP in the configuration (as of V3.0)
Note
First BaseUnit of an ET 200SP in the configuration
When an AC I/O module or AI Energy Meter ST is plugged, the first BaseUnit in an ET 200SP
station may be a dark one. Please note the information on limiting the overvoltage and
power rating in the AC I/O module manuals.
In order to route the 24 V DC supply voltage via a fuse, a light BaseUnit must be plugged into
the slot of the first 24 V DC I/O module.
Pay attention to the type of the BaseUnits during the configuration.
As of firmware V3.x, the interface modules support plugging dark BaseUnits in slot 1. This
means that modules without a connection to the integrated voltage buses P1 and P2 can now
also be configured starting with slot 1. Currently, this applies to the following modules:
•
DI 4x120..230VAC ST (6ES7131-6FD00-0BB1)
•
DQ 4x24..230VAC/2A ST (6ES7132-6FD00-0BB1)
Requirement for configuration of these modules in slot 1:
•
Configuration via GSD or GSDML
•
Configuration as of STEP 7 V5.5 SP4 with
–
HSP0241 V2.0 for IM155-6 PN ST
•
Configuration as of STEP 7 V13 SP1