Technical specifications
IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0)
42
Equipment Manual, 10/2020, A5E03576904-AE
Article number
6ES7155-6AU01-0BN0
•
Address space per module, max.
256 byte; per input / output
Address space per station
•
Address space per station, max.
512 byte; Dependent on configuration
Hardware configuration
Rack
•
Quantity of operable ET 200SP modules,
max.
32
•
Quantity of operable ET 200AL modules,
max.
16
Submodules
•
Number of submodules per station, max.
256
Interfaces
Number of PROFINET interfaces
1; 2 ports (switch)
1. Interface
Interface types
•
Number of ports
2
•
integrated switch
Yes
•
BusAdapter (PROFINET)
Yes; compatible BusAdapters: BA 2x RJ45, BA 2x
FC, BA 2x M12
Protocols
•
PROFINET IO Device
Yes
•
Open IE communication
Yes
•
Media redundancy
Yes; PROFINET MRP
Interface types
RJ 45 (Ethernet)
•
Transmission procedure
PROFINET with 100 Mbit/s full duplex (100BASE-
TX)
•
10 Mbps
Yes; for Ethernet services
•
100 Mbps
Yes; PROFINET with 100 Mbit/s full duplex
(100BASE-TX)
•
Autonegotiation
Yes
•
Autocrossing
Yes
Protocols
PROFINET IO Device
Services
–
IRT
Yes; with send cycles of between 250 µs and 4 ms
in increments of 125 µs
–
PROFIenergy
Yes
–
Prioritized startup
Yes
–
Shared device
Yes
–
Number of IO Controllers with shared
device, max.