User´s Guide Power Rail Booster
Version 12/2005
Copyright
©
Siemens AG 2005 All rights reserved.
6ES7 972-4AA02-0XA0
Page 38 of 49
Power Rail Booster
Immunity to high-frequency discharge
Testing following EN 61000-4-3:Frequency range 80
MHz - 1 GHz, test field intensity: 10 V/m at 80%
amplitude modulation with 1 kHz. Range 87 MHz
to108 MHz, 174 MHz to 230 MHz and 470 MHz to 790
MHz: 3V/m
Immunity to conducted interference
Power and bus cables ± 2 kV (Burst) (EN61000-4-4)
Immunity to conducted interference (Surge) Power cables ± 1 kV symmetrical (Surge)
Bus cables ± 2kV unsymmetrical (EN61000-4-5)
Climatic service environment
Ambient temperature with preferred mounting 0 °C to +60 °C (IEC 68-2-1, IEC 68-2-2)
position
Ambient temperature with other mounting position 0 °C to +45 °C
Storage temperature
–40 °C to +70 °C (IEC 68-2-14)
Relative humidity
<95 %, no condensation (IEC 68-2-30)
Mechanical ambience conditions
Vibration during operation
10 to 58 Hz, 0,075 mm displacement;
58 to 150 Hz, 9,8 m/s 2 (1 g) acceleration
(IEC
68–2–6)
Vibration during transport
5 to 9 Hz, 3,5 mm displacement;
9 to 500 Hz, 9,8 m/s 2 (1 g) acceleration
Type of protection
IP20
Dimensions
90,1x132x75 (WxHxD) with top hat rail 7,5 mm
90,1x132x82,5 (WxHxD) with top hat rail 15 mm
Preferred mounting position
Horizontal installation on vertical wall
Weight
360g