Saving the set time delay: On pressing the reset button (5) permanently for approx. 8 s in the programming mode after setting the time delay, all LEDs (3) are 
red. If the reset button is released then, the diagnosis module stores the set time delay and switches on the outputs sequentially. Now the diagnosis module is 
in its normal operating mode again. If the reset button is not pressed within 30 s in the programming mode, the diagnosis module automatically switches back 
to the normal operation mode without storing a change of time delay. If the supply voltage fails during programming, there will also be no storage.  

!

 

Note: The outputs of the diagnosis module are disconnected during the programming mode. After manual or automatic leaving of programming mode as 

well as resumption of power supply after breakdown, the outputs will be switched on automatically! 

Installation instructions 

Installation on DIN rail (DIN EN 50022-35x7.5/15). The equipment must be installed vertically with the input terminals at the bottom and the output terminals at 
the top, in order to ensure adequate heat dissipation. A clearance of at least 50 mm must be allowed above and below the device. 
To snap the unit on to the DIN bar, hang it with its nose (A)

 into the bar (C) 

and press until the spring (B) 

snaps into place (see page 2). If difficulty is 

experienced in snapping the unit on to the bar, loosen the spring (B)



 slightly as described under "Removing the Power Supply Unit". To remove from the DIN 

bar, use a screw driver to loosen the spring (B) 

in the direction of the arrow. 

The 24 V DC supply voltage (8) must be connected in accordance with the national standards. It is only allowed to be connected to a power supply with "safe 
electrical isolation" in accordance with EN 60950.  

!

 

Note: The 0 V connection (7) of the device merely serves to supply the internal electronic circuits. The 0 V of the loads must be supplied directly to the 

power supply by means of separate lines.  
In Ex - applications must be guaranteed that installation is according to protection class IP 54. 

Connections and terminal assignment 

 

Terminals Function 

Clamping 

range 

Remarks 

Input +24 V 

+24 V input voltage connection (from "+" 
output of the power supply) 

0.33 to 10 mm

 

Screw terminals; use a screwdriver with 5 mm blade width; recommended 
tightening torque 1.2 Nm. 

 

 

 

 

Input 0 V 

0 V connection for supplying the internal 
electronic circuits (from "–" output of the 
power supply) 

0.22 to 4 mm

 

Screw terminals; use a screwdriver with 3.5 mm blade width; 
recommended tightening torque 0.5 to 0.7 Nm. 
Note: The 0 V of the loads must be supplied directly to the power supply by 
means of separate lines !

 

 

Output 
1, 2, 3, 4  

Outputs of the diagnosis module for 
connecting the load circuits 
 

0.22 to 4 mm

 

Screw terminals; use a screwdriver with 3.5 mm blade width; 
recommended tightening torque 0.5 to 0.7 Nm. 

13, 14  

Common signaling contact 
 

0.22 to 4 mm

 

Screw terminals; use a screwdriver with 3.5 mm blade width; 
recommended tightening torque 0.5 to 0.7 Nm. 
 

Disconnection characteristic (typical)

 

 

Supply voltage > 20 V and the following power requirement for the branch concerned:  

 0 % to 100 % of setting   

  No disconnection 

 101 % to 130 % of setting 

  Disconnection after approx. 5 s 

 > 130 % of setting      

  Current limited to approx. 130 %, disconnection after typ. 50 to 100 ms 

Supply voltage dip < 20 V and the following power requirement for the branch concerned: 

 > 100 % of setting 

 

  Immediate disconnection 

 
 
 

 

Herausgegeben von:

 

SIMEA 

Bereich IA SC 

Siemensstraße 92 

1210 Wien 

Österreich 

Published by:

 

SIMEA 

IA SC Group 

Siemensstraße 92 

1210 Vienna 

Austria 

©  Siemens AG Österreich 08/2013. All rights reserved

Liefermöglichkeiten und technische Änderungen vorbehalten

Availability and technical specifications subject to change without prior notice

Bestellnummer / Order number C98130-A7524-A1-7-7419

 

5,0sec

0,10sec

0,0sec

0,1sec

1,0sec

10,0sec

100,0sec

0%

20%

40%

60%

80% 100% 120% 140% 160%

I / Irated

t

Содержание 6EP1961-2BA00

Страница 1: ...er Instandhaltung berücksichtigen Weiterführende Hinweise erhalten Sie über die örtliche Siemens Niederlassung bzw über die Homepage http www siemens de sitop Technische Änderungen jederzeit vorbehalten In Zweifelsfällen gilt der deutsche Text Note These operating instructions do not purport to cover all details of the product nor to provide for every possible contingency that may arise during ins...

Страница 2: ...013 Printed in Austria 94 max 5 71 5 90 1 2 3 reset 13 4 14 2 A 10 A 24V 0V output s 1 2 3 4 6EP1 961 2BA00 3 2 1 3 2 1 Q6NO green on red off input max 15A SITOP select 1 2 3 4 6 6 7 8 5 Maßbild Dimension drawing Montagehinweis Installation instruction Prinzipschaltplan Block diagram C B A ...

Страница 3: ...annung DC 24 V Arbeitsspannungsbereich DC 22 30 V Zuschaltschwelle ca 12 V Eingangsstrom max 40 A Ausgangsgrößen Ausgangsnennspannung DC 24 V entsprechend der Eingangsspannung Spannungsfall bei 10 A pro Abzweig typ 300 mV Einstellbereich der Abzweigstromes 2 10 A Einstellung mittels Potentiometer Parallelschaltung mehrerer Abzweige zur Leistungserhöhung ist nicht zulässig Strom bei abgeschaltetem ...

Страница 4: ...4 V DC Versorgungsspannung 8 muss gemäß den länderspezifischen Vorschriften ausgeführt werden und darf nur an eine Stromversorgung mit Sicherer elektrischer Trennung entsprechend EN 60950 angeschlossen werden Hinweis der 0 V Anschluss 7 des Gerätes dient lediglich der Versorgung der internen Elektronik die 0 V der Verbraucher sind über getrennte Leitungen direkt zur Stromversorgung zu führen Bei E...

Страница 5: ...iables Rated input voltage 24 V DC Working voltage range 22 V to 30 V DC Connection threshold Approx 12 V Max input current 40 A Output variables Rated output voltage 24 V DC equivalent to input voltage Typical voltage drop with 10 A per branch 300 mV Branch current setting range 2 A to 10 A set with potentiometer Parallel connection of several branches in order to increase the power is not permit...

Страница 6: ...n 7 of the device merely serves to supply the internal electronic circuits The 0 V of the loads must be supplied directly to the power supply by means of separate lines In Ex applications must be guaranteed that installation is according to protection class IP 54 Connections and terminal assignment Terminals Function Clamping range Remarks Input 24 V 24 V input voltage connection from output of th...

Отзывы: