A.4

Diagnostics messages and maintenance events

 [ID: 80188307851]

Diagnostics messages

A diagnostics message is generated for each diagnostics event and the DIAG LED on the RQ 

4x120VDC-230VAC/5A CO HA flashes red or the MT LED lights up yellow.
The diagnostics messages can be read in the diagnostics buffer of the CPU, for example.
Diagnostic messages are assigned either channel-specific to an output or assigned as module 

messages to all outputs. All channels are switched off for diagnostics messages that affect the 

entire module. Only the corresponding relay contact is affected by diagnostics messages, 

which refer to individual channels.

Table A-1

Diagnostics messages, their meanings and corrective measures

Diagnostics mes‐

sage

Error code Assignment

Meaning

Solution

Parameter as‐

signment error

10

H

Module

● Parameter assignment does not 

match the terminal block used

● Incorrect parameter assignment

● Correct the parameter 

assignment

● Check terminal block

1

Supply voltage 

missing

11

H

Module

Missing or insufficient supply volt‐

age L+

Check the supply voltage L+ 

on the terminal block

Channel/compo‐

nent temporarily 

unavailable

1F

H

Module

Firmware update is currently in pro‐

gress or has been canceled. The 

module does not output any process 

or substitute values in this state.

● Restart firmware update
● Wait for firmware update

Shutdown on but‐

ton activation

122

H

Module

The output disable switch was activa‐

ted

Pull and plug module

Retentive memo‐

ry in carrier mod‐

ule defective

154

H

Module

An error of the memory block on the 

adapter module was detected during 

startup

Replace carrier module 

Retentive memo‐

ry in the terminal 

block defective

155

H

Module

An error of the memory block on the 

terminal block was detected during 

startup

Replace terminal block

1

Only the terminal blocks (TB 45 ...) are suitable for operating I/O modules with IO redundancy. 

Maintenance events

A maintenance event is generated for each maintenance required identified. The MT LED 

lights up on the module.

Drivers, parameters, diagnostics messages and address space
A.4 Diagnostics messages and maintenance events

Digital Output Module RQ 4x120VDC-230VAC/5A CO HA (6DL1132-6HD50-0PK0)

34

Manual, 11/2017, A5E39389042-AC

Содержание 6DL1132-6HD50-0PK0

Страница 1: ...120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 Manual 11 2017 A5E39389042 AC Security information 1 Product overview 2 Wiring 3 Parameters 4 Displays and interrupts 5 Technical specifications 6 Drivers parameters diagnostics messages and address space A ...

Страница 2: ...l are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation If products and components from other manufacturers are us...

Страница 3: ...parameters 17 5 Displays and interrupts 19 5 1 Status and error displays of the I O module RQ 4x120VDC 230VAC 5A CO HA 19 5 2 Interrupts 21 6 Technical specifications 23 6 1 Switching cycles 26 A Drivers parameters diagnostics messages and address space 27 A 1 Concept of the driver and diagnostics blocks 27 A 2 Parameter assignment 29 A 3 Parameter assignment and structure of the module channel pa...

Страница 4: ...Table of contents Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 4 Manual 11 2017 A5E39389042 AC ...

Страница 5: ...Siemens products and solutions undergo continuous development to make them more secure Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used Use of product versions that are no longer supported and failure to apply the latest updates may increase customer s exposure to cyber threats To stay informed about product up...

Страница 6: ...ormation on the product described in the documentation on the handling of the product and on the section of the documentation to which particular attention should be paid Security information Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 6 Manual 11 2017 A5E39389042 AC ...

Страница 7: ... 4 PWR 6DL1132 6HD50 0PK0 Module type and designation Output disable switch LED for diagnostics Module type color coding LED for maintenance Product version 2D matrix code Function status and firmware version Wiring diagram Color code for selection of the color coded labels LEDs for channel status Serial number LED for supply voltage Article number Figure 2 1 View of the RQ 4x120VDC 230VAC 5A CO H...

Страница 8: ...tions Firmware update I M identification data Parameter reassignment in RUN Value status QI You can configure the I O module with HW Config and integrate it into your system Output disable switch If you want to pull the I O module in runtime you have to press the output disable switch for 3 seconds for the I O module to be deenergized Note that the NC contact is closed in this state When the outpu...

Страница 9: ...ly Labeling strips Color coded labels Reference identification label Shield connector Product overview 2 1 Properties of the I O module RQ 4x120VDC 230VAC 5A CO HA Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 Manual 11 2017 A5E39389042 AC 9 ...

Страница 10: ...Product overview 2 1 Properties of the I O module RQ 4x120VDC 230VAC 5A CO HA Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 10 Manual 11 2017 A5E39389042 AC ...

Страница 11: ...e You can find additional information on the configuration in the system manual WARNING Risk of death or serious injury from electric shock Prior to working on the system and module always disconnect them from the power supply NOTICE External fuse for relay outputs The outputs have to be protected with an external safety fuse with a maximum trip current of 6 A The fuse has to be a micro fuse with ...

Страница 12: ...2P 7 2 8 1 0 11 2 3 2 4 5 0 3 1 3 1 6 1P1 L 24VDC M 1P2 2P1 L 24VDC M 2P2 MAX 10 A 9 0 14 10 11 2 12 1 3 0 14 2 16 1 3 13 12 15 3 COM2 4 COM3 5 COM0 6 COM1 7 COM2 8 COM3 9 C0 10 C1 11 C2 12 C3 13 O0 14 O1 15 O2 16 O3 1P1 L 1P2 M 2P1 L 2P2 M 2Q 20Q Q Note You can use the two COM ports for each channel for looping this signal through Note that the maximum current capacity is 5 A Wiring 3 1 Pin assig...

Страница 13: ...C 5A CO HA 7 63 DFNSODQH EXV LQWHUIDFH DFNSODQH EXV 5HYHUVH SRODULW SURWHFWLRQ KDQQHO KDQQHO KDQQHO KDQQHO 3LQ 3LQ 3LQ 3LQ 0 Figure 3 1 Block diagram RQ 4x120VDC 230VAC 5A CO HA Wiring 3 2 Schematic circuit diagram Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 Manual 11 2017 A5E39389042 AC 13 ...

Страница 14: ...Wiring 3 2 Schematic circuit diagram Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 14 Manual 11 2017 A5E39389042 AC ...

Страница 15: ...111115 Configuring You configure the I O module with PCS 7 V9 0 or higher Parameters You define the functioning of the I O module via parameters See also Parameter assignment Page 29 Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 Manual 11 2017 A5E39389042 AC 15 ...

Страница 16: ...ctivated Enabled Disabled Enabled Yes Channel Reaction to CPU STOP Turn off Keep last value Output substitute value Turn off Yes Channel Substitute value 1 0 1 0 Yes Channel Potential group Use potential group of the left module Allow new potential group Use potential group of the left module No Module 1 Only in effect when Substitute value has been enabled for the Reaction to CPU STOP parameter P...

Страница 17: ... supply voltage A potential group begins with a light terminal block via which the required supply voltage is fed to all I O modules of the potential group The light colored terminal block interrupts the self assembling voltage buses to the left neighbor All other I O modules of this potential group are plugged into dark terminal blocks I O modules on dark terminal blocks take the potential of sel...

Страница 18: ...Parameters 4 3 Explanation of the module channel parameters Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 18 Manual 11 2017 A5E39389042 AC ...

Страница 19: ... 24VDC 24VDC M 1P2 2P1 LP M 2P2 MAX 10 A 0 1 2 3 V 1 0 0 CC40 PWR 6DL1132 6HD50 0PK0 X 2 3 4 DIAG LED green red MT LED yellow Channel status LED green PWR LED green Figure 5 1 LED displays Meaning of the LED displays The following tables show the meaning of the status and error displays Measures for dealing with diagnostics messages can be found in the section Diagnostics messages and maintenance ...

Страница 20: ...nce required On Maintenance is required i e at least one maintenance event has occurred Channel status LED Table 5 3 Status display of the channel status LED Channel status LED Meaning Off Process signal 0 or channel disabled On Process signal 1 and channel enabled PWR LED Table 5 4 Status display of the PWR LED PWR LED Meaning Off Supply voltage L missing On Supply voltage L available Displays an...

Страница 21: ...pply voltage missing Retentive memory in carrier module defective Retentive memory in the terminal block defective Shutdown on button activation Maintenance messages The I O module generates a maintenance message for the following events Retentive memory in carrier module defective Retentive memory in the terminal block defective Displays and interrupts 5 2 Interrupts Digital Output Module RQ 4x12...

Страница 22: ...Displays and interrupts 5 2 Interrupts Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 22 Manual 11 2017 A5E39389042 AC ...

Страница 23: ...missible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Input current Current consumption rated value 50 mA At 24 V and energized changeover coils Current consumption max 60 mA At 19 2 V and energized changeover coils Power loss Power loss typ 2 8 W At 24 V energized changeover coils and 5 A current across each changeover contact Address area Ad...

Страница 24: ... m Interrupts diagnostics status information Diagnostics function Yes Substitute values connectable Yes Alarms Diagnostic alarm Yes Diagnostic messages Monitoring the supply voltage Yes parameterizable Yes Diagnostics indication LED MAINT LED Yes yellow LED Monitoring of the supply voltage PWR LED Yes green PWR LED Channel status display Yes Green LED for module diagnostics Yes green red DIAG LED ...

Страница 25: ...llation min 40 C No icing horizontal installation max 70 C vertical installation min 40 C No icing vertical installation max 60 C Extended ambient conditions relative to ambient temperature atmospheric pressure installation altitude 3 000 m due to converter type used Dimensions Width 22 5 mm Height 115 mm Depth 138 mm Weights Weight approx 162 g Technical specifications Digital Output Module RQ 4x...

Страница 26: ...lion 0 5 A 0 8 million 0 1 A 1 million 60 VDC 1 0 A 0 5 million 0 5 A 0 8 million 0 1 A 1 million 120 V DC 0 1 A 1 million For resistive load 48 VAC to 230 VAC 5 0 A 0 1 million 3 0 A 0 2 million 2 0 A 0 3 million 1 0 A 0 5 million 0 5 A 0 8 million 0 1 A 1 million With inductive load 24 V DC 2 0 A 0 1 million 1 0 A 0 3 million 0 5 A 0 5 million 0 1 A 1 million 48 V DC 1 0 A 0 3 million 0 5 A 0 5 ...

Страница 27: ...7 library that implement the interface to the hardware including test functions These blocks perform two basic tasks They provide signals from the process to the AS for further processing They monitor modules DP PA slaves and DP master systems for failure When the process signals are read in these blocks access the process image input or process image partition PII and when the process signals are...

Страница 28: ...have to specify the version of the driver library from which the driver blocks are to be imported in the Generate module drivers dialog box Time optimized processing To enable time optimized processing during runtime the organization blocks for error handling for example OB85 OB86 are automatically divided into runtime groups and the driver blocks are integrated in the corresponding runtime groups...

Страница 29: ...specific extension of the error code Module specific errors are displayed via Error_Decode 0x80 and Error_Code_1 Error_Code_2 Error_ Code_ 1 Error_ Code_ 2 Cause Solution 0xB0 0x00 Number of the data record unknown Enter valid number for data record 0xB1 0x01 Length of the data record is incorrect Enter valid value for data record length 0xB2 Varia ble Module cannot be reached Check station is the...

Страница 30: ...is detected the entire data record is rejected and the parameters of the module remain unchanged Drivers parameters diagnostics messages and address space A 2 Parameter assignment Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 30 Manual 11 2017 A5E39389042 AC ...

Страница 31: ...tes each LJLWDO RXWSXW KDQQHO KDQQHO KDQQHO KDQQHO WH WH WH WH LJLWDO RXWSXW LJLWDO RXWSXW LJLWDO RXWSXW HDGHU LQIRUPDWLRQ PRGXOH WH HDGHU LQIRUPDWLRQ FKDQQHO WH 0RGXOH SDUDPHWHUV WH Figure A 1 Structure of data record 128 Drivers parameters diagnostics messages and address space A 3 Parameter assignment and structure of the module channel parameters Digital Output Module RQ 4x120VDC 230VAC 5A CO ...

Страница 32: ...JH HQJWK RI WKH PRGXOH SDUDPHWHU EORFN WH 5HVHUYHG WH WH WH WH 1XPEHU RI IROORZLQJ FKDQQHO SDUDPHWHU EORFNV HQJWK RI D FKDQQHO SDUDPHWHU EORFN WH WH WH 5HVHUYHG 5HVHUYHG 5HVHUYHG 5HVHUYHG Figure A 2 Header information and module parameters of data record 128 Drivers parameters diagnostics messages and address space A 3 Parameter assignment and structure of the module channel parameters Digital Out...

Страница 33: ...el parameter by setting the corresponding bit to 1 or to the appropriate value WH KDQQHO HQDEOHG ORFN 5HOHDVH 6XEVWLWXWH YDOXH 6XEVWLWXWH YDOXH 6ZLWFK RII HHS ODVW YDOXH 2XWSXW VXEVWLWXWH YDOXH 6XEVWLWXWH YDOXH EHKDYLRU 6XEVWLWXWH YDOXH WH 5HVHUYHG Figure A 3 Structure byte x to x 1 for the channels 0 to 3 Drivers parameters diagnostics messages and address space A 3 Parameter assignment and struc...

Страница 34: ...Missing or insufficient supply volt age L Check the supply voltage L on the terminal block Channel compo nent temporarily unavailable 1FH Module Firmware update is currently in pro gress or has been canceled The module does not output any process or substitute values in this state Restart firmware update Wait for firmware update Shutdown on but ton activation 122H Module The output disable switch ...

Страница 35: ... Module Fault detected in the data block on the carrier module during operation Replace carrier module Retentive memo ry in the terminal block defective 155H Module An error of the memory block on the terminal block was detected during operation Replace terminal block Drivers parameters diagnostics messages and address space A 4 Diagnostics messages and maintenance events Digital Output Module RQ ...

Страница 36: ...ere is a bit value status for each digital output in the input address space Irrespective of the diagnostics enables each value status each QI bit provides information on the validity of the corresponding process value Value status 1 Process value okay good Value status 0 Process value not okay bad Basically the value status is set to good if the digital value can be output without error The value...

Страница 37: ... P Parameters 15 16 Pin assignment 12 PWR LED 20 R RQ 4x120VDC 230VAC 5A CO HA Accessories 9 Channel parameters 16 Functions 8 Module parameters 16 Parameter 15 16 Parameters 16 Pin assignment 12 Properties 8 Schematic circuit diagram 13 Technical specifications 23 S Schematic circuit diagram 13 T Technology parameters 31 Terminal block 11 V Value status 36 Evaluating 36 Digital Output Module RQ 4...

Страница 38: ...Index Digital Output Module RQ 4x120VDC 230VAC 5A CO HA 6DL1132 6HD50 0PK0 38 Manual 11 2017 A5E39389042 AC ...

Отзывы: