Technical specifications
6
[ID: 80188333963]
Technical specifications of the RQ 4x120VDC-230VAC/5A CO HA
Article number
6DL1132-6HD50-0PK0
General information
Product type designation
RQ 4x120VDC-230VAC/5A CO HA
HW functional status
FS01
Firmware version
V1.0
● FW update possible
Yes
Usable terminal block
TB type K0
Color code for module-specific color identifica‐
tion plate
CC40
Product function
● I&M data
Yes; I&M0 to I&M3
Engineering with
● PCS 7 configurable/integrated as of version V9.0
Redundancy
● Redundancy capability
No
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Input current
Current consumption (rated value)
50 mA; At 24 V and energized changeover coils
Current consumption, max.
60 mA; At 19.2 V and energized changeover coils
Power loss
Power loss, typ.
2.8 W; At 24 V, energized changeover coils and 5
A current across each changeover contact
Address area
Address space per module
● Address space per module, max.
1 byte; + 1 byte for QI information
Digital outputs
Number of digital outputs
4
Switching frequency
● with resistive load, max.
2 Hz
● with inductive load, max.
0.5 Hz
● on lamp load, max.
2 Hz
Total current of the outputs
Digital Output Module RQ 4x120VDC-230VAC/5A CO HA (6DL1132-6HD50-0PK0)
Manual, 11/2017, A5E39389042-AC
23