Document Number 550-308 

Installation Instructions 

Rev. 1, July, 2001 

Siemens Building Technologies, Inc. 

Page 3 of 9

 

9.  After viewing Figure 6, install a clamp-on ferrite 

filter on the room temperature sensor cable and 
plug the cable into the RTS port on the controller 
(Figure 1). Use only an approved 588-100 series 
cable as described in the 

Product Numbers

 

section. Consider strain relief to ensure long-
term effectiveness due to added weight of the 
filter. 

10.  Connect the power trunk as shown in Figure 5. 

DO NOT apply power to the controller. 

11.  Connect the tubing from the air velocity sensor 

pickups to the HI and LO ports on the controller, 
or on the Autozero Modules (if present). Make 
sure that the “HI” and the “LO” pressure sides of 
the sensors are connected to the corresponding 
“HI” and “LO” sensor ports on the controller or 
Autozero Modules (Figure 2).  

The installation is complete.  

Replacement Instructions 

 

CAUTION: 

 

Replacement of a TEC requires you to 
record, re-enter, or update the initial point 
values of the controller being replaced. 
These are the points marked with an 
asterisk (*) on the CIS display.

 

NOTE: 

CIS Rev. 2.0 or higher is required for 
controller replacement. 

1.  Place the ESD wrist strap on your wrist and 

attach it to a good earth ground. 

2.  Before disconnecting the old controller, do 

one

 

of the following: 

NOTE: 

If the new controller has a newer 
firmware revision than the old 
controller, skip to the third bullet. 

• 

If the old controller communicates with the 
field panel, update the controller initial values 
at the field panel. 

• 

If the old controller does not communicate 
with the field panel, but communicates with 
CIS, or is stand-alone, record the initial 
values in Table 1. 

• 

If the old controller is not communicating or 
has a newer firmware revision, use the 
following steps to update the field panel: 

a.  Obtain a field panel Point Definition 

Report for the LCTLR point. Record the 
values in Table 1. 

b.  View the initial value block. (This 

information is valid only since the last 
update was made). Record the values in 
Table 1. 

c.  Delete the LCTLR point from the field 

panel. 

3.  Replace the old controller as follows: 

a.  Remove power from the controller. 

b.  If the old controller has the RTS plug 

between the FLN and point terminations, 
disconnect the wires from the power trunk 
terminal block. If the old controller has the 
RTS plug on the opposite end of the board 
from the power trunk terminal block, remove 
the power trunk terminal block. 

c.  Remove, in order, the controller’s: 

• 

FLN terminal block 

• 

Point wiring 

• 

Room temperature sensor 

d.  Remove the old controller assembly from the 

mounting rail. 

e.  Carefully remove the new controller 

assembly from the anti-static bag. Center it 
over the mounting rail and snap it securely 
into place. 

f.  If the old controller has the RTS plug 

between the FLN and point terminations, 
remove all terminal blocks (except the power 
trunk) from the new controller. If the old 
controller has the RTS plug on the opposite 
end of the board from the power trunk 
terminal block, remove all terminal blocks. 

g.  Plug, in order, the controller’s: 

• 

Pre-wired FLN 

• 

Point wiring 

NOTE: 

Wiring to DI3/AI3 requires a clamp-on 
ferrite filter (Figure 6). Strain relief 
must be provided to ensure long-term 
effectiveness due to added weight of 
the filter. 

Содержание 550-506

Страница 1: ...50 ft 15 2 m 588 100C 2 RJ11 room temperature sensor cable 100 ft 30 48 m 550 705 clamp on ferrite filter 10 pack Caution Notation CAUTION Equipment damage or loss of data may occur if the user does not follow procedure as specified Required Tools Electro Static Discharge ESD wrist strap Small flat blade screwdriver Medium flat blade screwdriver Medium duty electric drill 1 4 inch 6 35 mm hex nut ...

Страница 2: ... 6 or No 8 screws 3 Place the ESD wrist strap on your wrist and attach it to a good earth ground 4 Carefully remove the controller assembly from the anti static bag Center it over the mounting rail and snap it securely into place 5 Connect the Floor Level Network FLN See Figure 4 6 Connect the point wiring as shown in Figure 7 NOTE Wiring to DI3 AI3 requires a clamp on ferrite filter Figure 6 Stra...

Страница 3: ...ield panel If the old controller does not communicate with the field panel but communicates with CIS or is stand alone record the initial values in Table 1 If the old controller is not communicating or has a newer firmware revision use the following steps to update the field panel a Obtain a field panel Point Definition Report for the LCTLR point Record the values in Table 1 b View the initial val...

Страница 4: ... the new controller the field panel will automatically send the initial values down to the new controller Once this takes place replacement is complete If you manually recorded the initial values in the table then enter them into the new controller If a field panel is present then update the controller s initial values Replacement is complete If there was no communication at the old controller or ...

Страница 5: ...ARENTHESES 4 1 8 105 10 29 32 277 3 16 5 TEC0319R1 C L 11 9 32 287 1 27 32 47 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 S Figure 3 Mounting Dimensions FLN TRUNK RX TX S BST RTS SHIELD SHIELD TEC0272R2 NOTE DO NOT ground the shield 24 V AC H C GND DO1 DO2 DO3 DO4 DO5 NO C NO C NO C NO C NO C NO 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 1 COMMON 24 VAC HOT EARTH GND CONTROLLER POWE...

Страница 6: ...or point wiring for AI3 DI3 approximately 1 cm from the end 2 Wind the cable tightly twice around the filter 3 Close the filter and wrap it with a zip tie covering wound cable Figure 6 Adding Ferrite Filter s for CE Compliance CAUTION Ferrite filter s must be installed on the room temperature sensor RTS cable and any wiring to AI3 DI3 If not the controller is not CE compliant ...

Страница 7: ... 2 DO 7 NO C DO 8 NO C 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 C H GND S E H C Y1 G Y2 CW COMMON CCW COLD DUCT DAMPER ACTUATOR Y1 G Y2 CW COMMON CCW HOT DUCT DAMPER ACTUATOR ELECTRIC HEAT STAGE 2 OPTIONAL OR SPARE DO ELECTRIC HEAT STAGE 1 OPTIONAL OR SPARE DO AVS 2 AUTOZERO MODULE OPTIONAL OR SPARE DO Figure 7 Point Wiring for Applications 2237 2238 2267 and 2268 with Electric Reheat 1 ...

Страница 8: ... 12 13 14 15 16 17 18 19 20 C H GND S E H C Y1 G Y2 CW COMMON CCW COLD DUCT DAMPER ACTUATOR Y1 G Y2 CW COMMON CCW HOT DUCT DAMPER ACTUATOR ELECTRIC HEAT STAGE 2 OPTIONAL OR SPARE DO ELECTRIC HEAT STAGE 1 OPTIONAL OR SPARE DO AVS 2 AUTOZERO MODULE OPTIONAL OR SPARE DO DUCT TEMPERATURE SENSOR 100K THERMISTOR OPTIONAL Figure 9 Point Wiring for Application 2269 with Electric Reheat 1 2 3 4 5 6 7 8 9 1...

Страница 9: ...IL 60089 4513 U S A Your feedback is important to us If you have comments about this document please send them to technical editor sbt siemens com Document No 550 308 Printed in the U S A Page 9 NOTE Record only those points marked with an asterisk on the CIS display Use F3 Look to identify the initial value for each point marked with an asterisk You may want to make extra copies of this table for...

Отзывы: