Earthing
Connecting to earth
Connect the vacuum circuit-breaker on the earth terminal (70.) to the high-voltage
protective earth as specified (DIN EN 50341).
• Fully unscrew hexagon socket head screw M12 with washer on the earth
terminal (70.).
• Tighten ring terminal for the earth wire with the M12 hexagon screw and washer
on the earth terminal (70.) with 40 Nm.
Connect low-voltage
Connect the low-voltage connecting cables in the customer's switch cabinet in such
a way that safe operation as per supplied circuit diagram is guaranteed.
Note
If the 3AH37/38 vacuum circuit-breaker is installed into an earthed metal frame
and is connected permanently and electrically conductive, no separate earthing
needs to be done.
Place serrated washers under the screw heads when fastening the vacuum
circuit-breaker in this case.
Fig. 61
Earth terminal
Fig. 62
Connecting earth wire