Mounting position
The 3AH37/38 vacuum circuit-breaker can be installed indoors and vertically or
horizontally (optionally, mechanism box at the bottom) in relation to the interrupters.
Mounting the partitions
Carefully take the partitions out of the packaging (see Fig. 4) and mount according
to the supplied mounting drawing.
Mounting the vacuum circuit-breaker
There are a total of 14 fixing holes on the pole plate (15) and on the mechanism
box (60.) for the various types of installation.
Use M12 screws – strength class 8.8 – for fastening. The binding dimension
drawings are relevant.
The framework must be made to suit the operating conditions and have sufficient
load bearing capacity and stability.
Fig. 57
Mounting position
Fig. 58
Example of mounted partitions