Figure 16: Magnetic-actuator operator mechanism lubrication
Klüber L32 or Klüber L32N
K
K
K
K
K
K
K
K
K
K
K
K
K
f) Verify main contact status indicator
shows OPEN.
5. Refer to notice on page 27 to prevent
damage due to electrostatic discharge.
De-energize the control power by
opening the control power disconnect
device in the relay and control
compartment. Fast discharge the
capacitors (106.2) by unplugging the
connector (105.2) on the capacitor
controller board (105.0). Do not unplug
connector (106.3) from the capacitor
boards, or damage to the capacitor
board or the controller board may occur.
6. After the fast-discharge process, plug in
the connector (105.2) on the controller
board (105.0).
When the capacitors are charged, press the
Close pushbutton (53.0). The CLOSE/OPEN
indicator (58.0) must indicate the CLOSED
position.
MLFB label