Analog value representation
4.3 Measuring ranges
2AI TC HF analog electronic module (6ES7134-4NB01-0AB0)
Manual, 04/2007, A5E01076892-01
23
Measuring range for thermocouple Types R, S
Table 4-10 SIMATIC S7 format: Type R, S measuring range in °C and °F
Units
Units
Type R, S in °C
Decimal Hexadecima
l
Type R, S in °F
Decimal
Hexadeci
mal
Range
> 2019,0
32767
7FFF
H
> 3276,6
32767
7FFF
H
Overflow
2019,0
:
1769,1
20190
:
17691
4EDE
H
:
451B
H
3276,6
:
3216,3
32766
:
32163
7FFE
H
:
7DA3
H
Overshoot range
1769,0
:
-50,0
17690
:
-500
451A
H
:
FE0C
H
3216,2
:
-58,0
32162
:
-580
7DA2
H
:
FDBC
H
Nominal range
-50,1
:
-170,0
-510
:
-1700
FE0B
H
:
F95C
H
-58,1
:
-274,0
-581
:
-2740
FDBB
H
:
F54C
H
Underrange
< -170,0
-32768
8000
H
< -274,0
-32768
8000
H
Underflow
Measuring range for thermocouple Type T
Table 4-11 SIMATIC S7 format: Type T measuring range in °C and °F
Units
Units
Type T in °C
Decimal Hexadecima
l
Type T in °F
Decimal
Hexadeci
mal
Range
> 540,0
32767
7FFF
H
> 1004,0
32767
7FFF
H
Overflow
540,0
:
400,1
5400
:
4001
1518
H
:
0FA1
H
1004,0
752,1
10040
7521
2738
H
1DC1
H
Overshoot range
400,0
:
-270,0
4000
:
-2700
0FA0
H
:
F574
H
752,0
:
-454,0
7520
:
-4540
1D60
H
:
EE44
H
Nominal range
< -270,0
-32768
8000
H
< -454,0
-32768
8000
H
Underflow