Analog value representation
4.3 Measuring ranges
2AI TC HF analog electronic module (6ES7134-4NB01-0AB0)
Manual, 04/2007, A5E01076892-01
21
Measuring range for thermocouple Type J
Table 4-6
SIMATIC S7 format: Type J measuring range in °C and °F
Units
Units
Type J in °C
Decimal Hexadecima
l
Type J in °F
Decimal
Hexadeci
mal
Range
> 1450,0
32767
7FFF
H
> 2642,0
32767
7FFF
H
Overflow
1450,0
:
1200,1
14500
:
12010
38A4
H
:
2EEA
H
2642,0
:
2192,1
26420
:
21921
6734
H
:
55A1
H
Overshoot range
1200,0
:
-210,0
12000
:
-2100
2EE0
H
:
F7CC
H
2192,0
:
-346,0
21920
:
-3460
55A0
H
:
F27C
H
Nominal range
< -210,0
- 32768
8000
H
< -346,0
- 32768
8000
H
Underflow
Measuring range for thermocouple Type K
Table 4-7
SIMATIC S7 format: Type K measuring range in °C and °F
Units
Units
Type K in °C
Decimal Hexadecima
l
Type K in °F
Decimal
Hexadeci
mal
Range
> 1622,0
32767
7FFF
H
> 2951,6
32767
7FFF
H
Overflow
1622,0
:
1372,1
16220
:
13721
3F5C
H
:
3599
H
2951,6
:
2501,7
29516
:
25062
734C
H
:
61B9
H
Overshoot range
1372,0
:
-270,0
13720
:
-2700
3589
H
:
F574
H
2501,6
:
-454,0
25061
:
-4540
61B8
H
:
EE44
H
Nominal range
< -270,0
- 32768
8000
H
< -454,0
- 32768
8000
H
Underflow