NOTE:

Not typical for all size switches

Circuit Breaker Assembly Instructions

Replacement Parts and Instruction Guide

E87010-A0137-T003-A4

Siemens Industry, Inc. 3617 Parkway Ln, Peachtree Corners, GA 30092   www.usa.siemens.com

         4         A5E31166526A-003    

5.    Install the new handle assembly onto the enclosure.

6.    Reinstall the two 1/4-20 screws and lock washers. 

       Make sure the handle housing is sealed against the                         

       enclosure flange as this prevents the entry of moisture.

7.    Reinstall the connecting pin and retaining ring that connect

       the handle link to the mechanism. The retaining ring should

       not spin freely on the shaft after it is installed.

8.    No handle adjustment is required.

9.    Verify that the handle mechanism turns ‘ON’ and ‘OFF’ the      

       circuit breaker.

10.   Verify that the door cannot be opened with the handle in  

        the ‘ON’ position.

1.    Remove the (2) screws from the connecting link.

2.     Use a 5/16” wrench to remove the two 1/4-20 screws and           

        lock washers which secure the handle to the enclosure           

        flange. These screws are located on the underside of the           

        enclosure flange. Remove the old handle assembly from           

        the enclosure.

3.     Remove the mechanism from the panel and replace it           

        with the one provided. The mounting panel may need to be           

        removed to access the mounting screws.

4.     Hardware has been provided to mount a new disconnect       

        switch if necessary. 

Содержание 17

Страница 1: ...sult if proper precautions are not taken Warning Indicates death severe personal injury or property damage can result if proper precautions are not taken Caution Indicates personal injury or property damage may result if proper precautions are not taken Short Circuit Explosion Hazard Can cause death serious personal injury or property damage Fully engage all door latches and spread ends of door hi...

Страница 2: ...itch Type Selection Disconnect Fuse Clip Ampere Rating 3 ED63A003 10 ED63A010 25 ED63A025 30 ED63A030 50 ED63A050 100 ED63A100 125 ED63A125 150 FXD63A150L B1 Disconnect Switch Handle and Mechanism Class 17 25 32 Enclosure Type 1 3R 4 4X 12 Disconnect Size Amps Enclosure Size Handle Assembly Only Handle Assembly Disc Mech 3 125 100 125 150 250 24 H x 11 W x 8 D 24 H x 20 W x 8 D 36 H x 24 W x 8 D A...

Страница 3: ...th primary fusing KT_ _ 150 is 150VA with primary fusing E Motor Starter or Contactor See device label for appropriate replacement parts sheet F Auxiliary Contacts Not Shown Auxiliary Contacts Installed on contactor 1NO G10 1 49AB10 2NO G20 1 49AB20 3NO G30 1 49AB20 1 49AB10 4NO G40 1 49AB40 1NC G01 1 49AB01 2NC G02 2 49AB01 1NO 1NC G11 1 49AB11 1NO 2NC G12 1 49AB12 2NO 1NC G21 1 49AB21 2NO 2NC G2...

Страница 4: ...link to the mechanism The retaining ring should not spin freely on the shaft after it is installed 8 No handle adjustment is required 9 Verify that the handle mechanism turns ON and OFF the circuit breaker 10 Verify that the door cannot be opened with the handle in the ON position 1 Remove the 2 screws from the connecting link 2 Use a 5 16 wrench to remove the two 1 4 20 screws and lock washers wh...

Страница 5: ...en provided to mount a new circuit breaker if necessary 5 Install the new handle assembly onto the enclosure 6 Reinstall the two 1 4 20 screws and lock washers Make sure the handle housing is sealed against the enclosure flange as this prevents the entry of moisture 7 Reinstall the two screws that connect the handle link to the pivot assembly 8 No handle adjustment is required 9 Verify that the ha...

Страница 6: ...ed to access the mounting screws 4 Hardware has been provided to mount a new circuit breaker if necessary 5 Install the new handle assembly onto the enclosure 6 Reinstall the two1 4 20 screws and lock washers Make sure the handle housing is sealed against the enclosure flange as this prevents the entry of moisture 7 Reinstall the two screws that connect the handle link to the pivot assembly 9 Veri...

Отзывы: