15
P13
Deviation bar graph resolution
(3 digit deviation bar only)
For an RTD input with a decimal place, P13 can be set from
0.2 to 20.0
°
C. For all other inputs, it can be set from 2 to 200
engineering units. P13 is the band around the setpoint at
which the deviation display changes (see graphic).
The configuration procedure is now complete. The
instrument should show “-.-.-.” on both displays. Press
the FUNC key; the instrument will return to the beginning
of the configuration procedure. To continue with controller
set-up go to the operating mode found in the next section.
To access the advanced configuration parameters
proceed as follows:
1) Use the
▲
and
▼
keys to enter 219 on the display.
2) Press the FUNC key.
Green
Red
Red
Flashing Red
Flashing Red
Deviation is greater than
1-1/2 times P13.
Deviation is between 1/2 and
1-1/2 times P13.
Deviation is less than
±
1/2 times P13.
Deviation is between 1/2 and
1-1/2 times P13.
Deviation is greater than 1-1/2 times P13.