P1
Input type and standard range
0
= TC type
L
range
0 to +800
°
C
1
= TC type
J
range
0 to +800
°
C
2
= TC type
K
range
0 to +999
°
C
3
= TC type
N
range
0 to +999
°
C
4
= RTD type
Pt 100
range
-199 to +500
°
C
5
= RTD type
Pt 100
range
-19.9 to +99.9
°
C
6
= TC type
T
range
0 to +400
°
C
8
= TC type
L
range
0 to +999
°
F
9
= TC type
J
range
0 to +999
°
F
10 = TC type
K
range
0 to +999
°
F
11 = TC type
N
range
0 to +999
°
F
12 = RTD type
Pt 100
range
-199 to +999
°
F
13 = TC type
T
range
0 to +400
°
C
NOTE: If using
°
C, add the label (located on the INDEX
page) to the front of the instrument.
P2
Span low
Not present when P1 = 5.
Enter the low end setting of the span.
P3
Span high
Not present when P1 = 5.
Enter the high end setting of the span.
NOTE: The minimum input span (P3 - P2) is 300
°
C or
600
°
F for a thermocouple input and 100
°
C or
200
°
F for an RTD input.
P4
Main output action
The 3 digit heat/cool controller skips this parameter when
P5 = 5.
r = Reverse acting (heating).
d = Direct acting (cooling).
P5
Output 2 function
0 = None
1 = Process alarm
2 = Band alarm
3 = Deviation alarm
4 = Instrument failure indicator
5 = Cooling output (3 digit heat/cool controller only)
NOTE: For the 3 digit heat/cool model, when parameter
P5 = 5, parameter P4 = “r”.
P6
Output 2 operating mode
Not available when P5 = 0.
If P5 = 1, 2 or 3:
H.A = High alarm (outside of the band) with
automatic reset.
L.A = Low alarm (inside the band) with automatic
reset.
H.L = High alarm (outside band) with manual reset.
L.L = Low alarm (inside band) with manual reset.
When P5 = 4:
Selections H.A and L.A indicate an instrument
failure with automatic reset while the H.L and L.L
selections indicate an instrument failure with
manual reset.
If P5 = 5:
(3 digit dual display model only) P6 selects the
cooling medium:
Alr = Air
OlL = Oil
H2O = Water
NOTE: Different cooling settings cause automatic
modification of both the relative cooling gain and
the cooling cycle time.
6
P
C
G
C
R
r
i
A
s
d
n
o
c
e
s
0
1
1
li
O
s
d
n
o
c
e
s
4
8
.
0
O
2
H
s
d
n
o
c
e
s
2
4
.
0
Содержание Barber Colman 7SD
Страница 1: ...1 Instruction Manual 1262 IN 001 0 03 July 1998 D Models 7SD 7SH 7SM Controllers...
Страница 30: ...30 Notes...
Страница 31: ...31 Notes...