FAULT DIAGNOSIS
8
75
80251340/2020-02-03|SICK
Subject to change without notice
T R A N S L A T I O N O F T H E O R I G I N A L O P E R A T I N G I N S T R U C T I O N S | VMS6200
8.2.2
Checking the incremental encoder
Fig. 56: Checking the incremental signals on the MSC800
If the incremental encoder has been connected correctly, the following LEDs should flash
when the conveying equipment is running:
Controller type
LED
MSC800
INC
terminal block, LEDs on the
INC_1
and
INC_2
connection.
If the LEDs do not flash, possible causes might be:
Cause
Remedy
There is no/insufficient
contact between the
measuring wheel and the
conveying equipment.
▸
Make sure that there is good contact between
the measuring wheel and the conveying equipment
on-site.
▸
If the measuring wheel shows signs of wear,
replace it.
Signal ground not activated.
▸
Set the
SGND_4
signal ground switch to
ON
.
Wire is not correctly attached
in the terminal block.
Check that the wires are attached correctly.
Encoder is defective.
Replace the device.
Tab. 16: Checking the incremental signals on the MSC800