FACTORY SETTINGS
13
Factory settings
The factory settings can be restored using the factory reset.
Parameter
Value
Measurement mode
Relative (%)
Medium
Water
Diameter
26 mm
Q1 switchpoint 1 - relative velocity
50%
Q1 switchpoint 2 - relative velocity
30%
Q1 switchpoint 1 - absolute velocity
0.5 m/s
Q1 switchpoint 2 - absolute velocity
0.3 m/s
Q1 switchpoint 1 - volume flow
16 L/min
Q1 switchpoint 2 - volume flow
9.5 L/min
Q1 switchpoint 1 - temperature
30 °C
Q1 switchpoint 2 - temperature
25 °C
Q1 mode
Flow hysteresis for normally open
Q2 switchpoint 1 - relative velocity
80%
Q2 switchpoint 2 - relative velocity
60%
Q2 switchpoint 1 - absolute velocity
0.8 m/s
Q2 switchpoint 2 - absolute velocity
0.6 m/s
Q2 switchpoint 1 - volume flow
25.5 L/min
Q2 switchpoint 2 - volume flow
19.0 L/min
Q2 switchpoint 1 - temperature
80 °C
Q2 switchpoint 2 - temperature
75 °C
Q2 mode - electrical version A
Flow hysteresis for normally closed
Q2 mode - electrical version B
Flow analog
Q2a analog lower limit - relative velocity
2%
Q2a analog upper limit - relative velocity
100%
Q2a analog lower limit - absolute velocity
0.03 m/s
Q2a analog upper limit - absolute velocity
1.5 m/s
Q2a analog lower limit - volume flow
1 L/min
Q2a analog upper limit - volume flow
40 L/min
Q2a analog lower limit - temperature
0 °C